Chiller has multiple loss of<br />

communication diagnostics.<br />

Using TechView go into binding<br />

view. Are there devices that are<br />

not verified?<br />

YES<br />

Check for 24 VAC at J2-1 <strong>and</strong><br />

J2-2 on the power supply.<br />

Check for 24 VDC at J1, J3, J4,<br />

<strong>and</strong> J11 between pins 1 <strong>and</strong> 2.<br />

Is the voltage within 22.8 to 25.2<br />

VDC?<br />

YES<br />

Try to bind the<br />

device(s). Did they<br />

bind?<br />

NO<br />

Can you turn all the<br />

LEDs on with a<br />

south pole magnet?<br />

YES<br />

Does the light stay<br />

on when the magnet<br />

is removed?<br />

YES<br />

IPC Overview <strong>and</strong> Troubleshooting<br />

YES<br />

NO<br />

NO<br />

NO<br />

NO<br />

Reset diagnostics<br />

Refer to Section 3-<br />

Power supply<br />

checkout .<br />

Reset diagnostics<br />

There is no Power<br />

at the LLID.<br />

Replace LLID<br />

Problem could be with the LLID<br />

bus, a connector or the LLID. If<br />

only one LLID is not functioning<br />

suspect the LLID or the<br />

connector. If problem is with<br />

multiple LLID suspect a problem<br />

with the LLID bus or a connector<br />

12 RLC-SVB05A-EN