CH530 provides compatibility with two types of starters for <strong>RTAC</strong> <strong>and</strong> <strong>RTHD</strong><br />
X-Line - <strong>RTAC</strong> only<br />
Y-Delta<br />
Solid State - <strong>RTHD</strong> only<br />
CH530 provides a “Start” contact closure output for across the line starters. To<br />
reduce the risk of starter damage due to the wrong starter type being selected,<br />
the Transition Complete input is required to be wired at the starter module.<br />
Individual relays on the CH530 Starter module control the timing sequence for<br />
the “Stop”, “Start”, “Short”, “Transition”, <strong>and</strong> “Run” contactor closures. During a<br />
motor start. Prior to closing the “Short” contact, the transition complete input is<br />
verified to be open, otherwise an MMR diagnostic is generated.<br />
The sequence of a Y-Delta Start is shown in Figure 14. A more elaborate<br />
description of the Y-delta starting sequence is shown in Figure 15 -Figure 28.<br />