Transducer Checkout Procedure<br />
Is the transducer<br />
bound <strong>and</strong><br />
communicating?<br />
CAUTION<br />
Equipment<br />
Damage Possible!<br />
Pressure Transducers<br />
All of the Pressure Transducers used on <strong>RTAC</strong> <strong>and</strong> <strong>RTHD</strong> units are mounted on<br />
service valves. Pressure Transducers measure absolute pressure. They have a<br />
range of 0 to 475 psia with an accuracy of ± 1.5 psi under steady state conditions.<br />
Figure 10.Pressure Transducer<br />
Connect TechView <strong>and</strong> get into Binding View. This will shut the chiller down.<br />
Once in Binding View verify that the Pressure Transducer is bound.<br />
Note: Please refer to Service Tool for questions concerning binding LLIDs <strong>and</strong><br />
getting into Binding View.<br />
If there are multiple LLIDs that are not verified go to IPC troubleshooting.<br />
If the transducer is not bound, try to bind it. If the transducer will not bind, it<br />
could be a problem with the connector or the sensor itself. Take a close look at<br />
the connector to make sure that all four wires are securely in place. It may be<br />
necessary to remove the cap to check for broken or misplaced wires.<br />
All units built before October 1, 2002 (U02#####) used connectors that must be<br />
replaced if the cap is removed. If the cap is removed on any of these units cut out<br />
the old connector <strong>and</strong> splice in a new section of cable <strong>and</strong> a new connector. See<br />
Section 2-IPC Overview for instruction on installing a new cap.<br />
If the transducer is bound, try to turn the LED on with a magnet. If the light will<br />
not turn on there could be a problem with the transducer. Try to turn the light on<br />
in Binding View. With the light on hold the magnet to the LED. The LED should<br />
get brighter. If it doesn’t get brighter, this may indicate a problem with the<br />
transducer or the connector. Take a close look at the connector to make sure that<br />
18 RLC-SVD05A-EN<br />
LED