Compressor Capacity - <strong>RTAC</strong><br />
The CHHP (GPII) compressor is a “screw” or helical rotor design with two rotors,<br />
one directly driven by the motor called the male <strong>and</strong> the other driven by the<br />
lobes of the male called the female.<br />
CHHP compressors have a female step load solenoid valve <strong>and</strong> male load/unload<br />
solenoid valves that are utilized for capacity control. The female step load<br />
solenoid is so named because it acts on the female rotor side of the compressor,<br />
<strong>and</strong> its function is to “pilot” a larger valve inside the compressor that opens to<br />
bypass compressed vapor back to the suction of the compressor. This bypass<br />
action causes a “step” difference in the capacity of the compressor.<br />
On the Male rotor side of the compressor is the male port unloader piston, which<br />
can move laterally along the male rotor. Small bypass ports in the rotor housing<br />
are covered <strong>and</strong> uncovered by the unloader piston as it moves. The position of<br />
the piston, is controlled by two direct acting solenoid valves called the male load<br />
<strong>and</strong> male unload solenoid valves. These valves add or vent pressure to the<br />
cylinder of the movable piston to position <strong>and</strong> “modulate” the amount of<br />
compressed vapor that can be bypassed back to suction.<br />
��������<br />
����<br />
���<br />
���<br />
��<br />
��<br />
���<br />
Figure 32.Compressor Capacity<br />
With the female solenoid de-energized (internal female bypass valve open), the<br />
minimum capacity of the compressor is 30% of full load. With the female<br />
solenoid valve energized, (<strong>and</strong> the male port unloader in the unloaded position)<br />
the compressor capacity jumps up to approximately 60%. Through pulsed<br />
control of the male load <strong>and</strong> unload solenoid valves, the piston can be moved to<br />
exactly modulate the load of the compressor from 60 to 100% of its capacity.<br />
There are no springs acting on the male port unloader piston, <strong>and</strong> as such, the<br />
piston can only be effectively moved while the compressor (or manifolded<br />
compressor) is running, creating differential pressure.<br />
48 RLC-SVD05A-EN<br />