Compressor Capacity - <strong>RTAC</strong><br />

The CHHP (GPII) compressor is a “screw” or helical rotor design with two rotors,<br />

one directly driven by the motor called the male <strong>and</strong> the other driven by the<br />

lobes of the male called the female.<br />

CHHP compressors have a female step load solenoid valve <strong>and</strong> male load/unload<br />

solenoid valves that are utilized for capacity control. The female step load<br />

solenoid is so named because it acts on the female rotor side of the compressor,<br />

<strong>and</strong> its function is to “pilot” a larger valve inside the compressor that opens to<br />

bypass compressed vapor back to the suction of the compressor. This bypass<br />

action causes a “step” difference in the capacity of the compressor.<br />

On the Male rotor side of the compressor is the male port unloader piston, which<br />

can move laterally along the male rotor. Small bypass ports in the rotor housing<br />

are covered <strong>and</strong> uncovered by the unloader piston as it moves. The position of<br />

the piston, is controlled by two direct acting solenoid valves called the male load<br />

<strong>and</strong> male unload solenoid valves. These valves add or vent pressure to the<br />

cylinder of the movable piston to position <strong>and</strong> “modulate” the amount of<br />

compressed vapor that can be bypassed back to suction.<br />

��������<br />

����<br />

���<br />

���<br />

��<br />

��<br />

���<br />

Figure 32.Compressor Capacity<br />

With the female solenoid de-energized (internal female bypass valve open), the<br />

minimum capacity of the compressor is 30% of full load. With the female<br />

solenoid valve energized, (<strong>and</strong> the male port unloader in the unloaded position)<br />

the compressor capacity jumps up to approximately 60%. Through pulsed<br />

control of the male load <strong>and</strong> unload solenoid valves, the piston can be moved to<br />

exactly modulate the load of the compressor from 60 to 100% of its capacity.<br />

There are no springs acting on the male port unloader piston, <strong>and</strong> as such, the<br />

piston can only be effectively moved while the compressor (or manifolded<br />

compressor) is running, creating differential pressure.<br />

48 RLC-SVD05A-EN<br />