Current Transformers<br />

Where:<br />

I0x = the phase with the largest difference from Iave.<br />

5 Current Limit. The current limit range for each compressor is 60-120% RLA for<br />

<strong>RTAC</strong> <strong>and</strong> 40-100% RLA for <strong>RTHD</strong>. The figure below provides a graphical<br />

illustration of the current limit control.<br />

��<br />

�����<br />

�����<br />

�������<br />

Figure 13 Current Limit Control<br />

RLC-SVD05A-EN 27<br />

����<br />

��� � ��� ��� � ��<br />

���<br />

��� � ��<br />

������<br />

������<br />

Note: The current transformers are NOT polarity or directionally sensitive in<br />

<strong>RTAC</strong> <strong>and</strong> <strong>RTHD</strong> applications<br />

CT <strong>and</strong> Starter Compressor Current Input Checkout Procedure<br />

� WARNING<br />

Live Electrical<br />

Components!<br />

Iave = I01+I02+I03<br />

During installation, testing, servicing <strong>and</strong> troubleshooting of this product, it may<br />

be necessary to work with live electrical components. Have a qualified licensed<br />

electrician or other individual who has been properly trained in h<strong>and</strong>ling live<br />

electrical components perform these tasks. Failure to follow all electrical safety<br />

precautions when exposed to live electrical components could result in death or<br />

serious injury.<br />

1 Check incoming 3-phase power for voltage within +/- 10% of nominal per<br />

Chiller nameplate. Verify that unit size <strong>and</strong> voltage are set correctly using<br />

TechView.<br />

2 Check for all of the active diagnostic codes or the historic diagnostic codes<br />

using TechView under Diagnostic View.<br />

If there is any question as to which compressor or current transformer is<br />

causing a problem, or simply to verify <strong>and</strong> “witness” the problem, an attempt<br />

should be made to start the chiller after resetting all diagnostics.<br />

It is possible to “force” specific compressors to be the first or next<br />

compressor to stage on, using the “Compressor Test” feature of Tech View in<br />

Compressor Service View. The Leaving Water Temperature must, however, be<br />

3<br />

���������� ����