Current Transformers<br />
Where:<br />
I0x = the phase with the largest difference from Iave.<br />
5 Current Limit. The current limit range for each compressor is 60-120% RLA for<br />
<strong>RTAC</strong> <strong>and</strong> 40-100% RLA for <strong>RTHD</strong>. The figure below provides a graphical<br />
illustration of the current limit control.<br />
��<br />
�����<br />
�����<br />
�������<br />
Figure 13 Current Limit Control<br />
RLC-SVD05A-EN 27<br />
����<br />
��� � ��� ��� � ��<br />
���<br />
��� � ��<br />
������<br />
������<br />
Note: The current transformers are NOT polarity or directionally sensitive in<br />
<strong>RTAC</strong> <strong>and</strong> <strong>RTHD</strong> applications<br />
CT <strong>and</strong> Starter Compressor Current Input Checkout Procedure<br />
� WARNING<br />
Live Electrical<br />
Components!<br />
Iave = I01+I02+I03<br />
During installation, testing, servicing <strong>and</strong> troubleshooting of this product, it may<br />
be necessary to work with live electrical components. Have a qualified licensed<br />
electrician or other individual who has been properly trained in h<strong>and</strong>ling live<br />
electrical components perform these tasks. Failure to follow all electrical safety<br />
precautions when exposed to live electrical components could result in death or<br />
serious injury.<br />
1 Check incoming 3-phase power for voltage within +/- 10% of nominal per<br />
Chiller nameplate. Verify that unit size <strong>and</strong> voltage are set correctly using<br />
TechView.<br />
2 Check for all of the active diagnostic codes or the historic diagnostic codes<br />
using TechView under Diagnostic View.<br />
If there is any question as to which compressor or current transformer is<br />
causing a problem, or simply to verify <strong>and</strong> “witness” the problem, an attempt<br />
should be made to start the chiller after resetting all diagnostics.<br />
It is possible to “force” specific compressors to be the first or next<br />
compressor to stage on, using the “Compressor Test” feature of Tech View in<br />
Compressor Service View. The Leaving Water Temperature must, however, be<br />
3<br />
���������� ����