Over/Under Voltage<br />
Table 6. Starter Module Input-to-Line Voltage Conversion<br />
Starter Module Input Voltage<br />
J5-1,2<br />
J5-3,4<br />
J5-5,6<br />
Incoming Line-to-Line Voltage<br />
(Volt AC)<br />
(Volt AC)<br />
14.4 290<br />
14.9 300<br />
15.4 310<br />
15.9 320<br />
16.3 330<br />
16.8 340<br />
17.3 350<br />
17.8 360<br />
18.3 370<br />
18.8 380<br />
19.3 390<br />
19.8 400<br />
20.3 410<br />
20.8 420<br />
21.3 430<br />
21.8 440<br />
22.3 450<br />
22.8 460<br />
23.3 470<br />
23.8 480<br />
24.3 490<br />
24.8 500<br />
25.3 510<br />
25.7 520<br />
26.2 530<br />
26.7 540<br />
27.2 550<br />
27.7 560<br />
28.2 570<br />
Acceptable tolerance between actual incoming line-to-line voltage <strong>and</strong> displayed<br />
voltage (on DynaView or TechView) is +\- 3% of reading. The accuracy of the<br />
meter being used to measure the actual line-to-line voltage needs to be added to<br />
this tolerance.<br />
Acceptable tolerance between the Starter module input voltage measurements<br />
listed Table 6 with respect to the displayed line-to line voltage (on DynaView or<br />
TechView) is +\- 3% of reading.<br />
32 RLC-SVD05A-EN