17.12.2012 Views

RTHD and RTAC - Trane

RTHD and RTAC - Trane

RTHD and RTAC - Trane

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

Is the EXV<br />

functioning<br />

properly?<br />

Electronic Expansion Valve<br />

the old connector <strong>and</strong> splice in a new section of cable <strong>and</strong> a new connector. See<br />

Section 2-IPC Overview for instruction on installing a new cap.<br />

If the EXV is bound, try to turn the LED on with a magnet. If the light will not turn<br />

on, there could be a problem with the EXV. Try to turn the light on in Binding<br />

View. With the light on, hold the magnet to the LED. The LED should get brighter.<br />

If it doesn’t get brighter, this may indicate a problem with the EXV or the<br />

connector. Take a close look at the connector to make sure that all four wires are<br />

securely in place. It may be necessary to remove the cap to check for broken or<br />

misplaced wires.<br />

If there is no problem found with the connector <strong>and</strong> the EXV will not bind, then<br />

replace the EXV.<br />

The EXV goes to the closed position at a normal shutdown. There is a sight glass<br />

in the body of the valve to monitor EXV position. Refer to Figure 35.<br />

Figure 35.EXV Position<br />

1 Shut the chiller down.<br />

2 Lock out the circuit. This can be done using DynaView under the setpoint tab<br />

or in TechView under the Compressor Service View. Refer to Figure 36. With<br />

the circuit shut down the valve should go to the closed position. Note the EXV<br />

position.<br />

3 Using TechView under Compressor Service View, open the EXV. Look at the<br />

EXV position. The valve should go to the open position. Refer to Figure 36.<br />

4 The valve should go from closed to full open. If the valve does not move or<br />

open fully, replace the valve.<br />

It is very important to confirm that the valve is bound <strong>and</strong> communicating on<br />

the LLID bus before it is replaced.<br />

5 Place the valve back into the auto mode of operation.<br />

RLC-SVD05A-EN 55

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!