External LLID Sensor<br />
Internal LLID<br />
The liquid level sensor is mounted in a small tank or canister attached to the<br />
outside of the tube sheet. The evaporator’s liquid level is transmitted into the<br />
tank through a small vapor <strong>and</strong> liquid line.<br />
The liquid level sensor is required to provide input for control of the EXV, which<br />
allows the regulation of refrigerant flow into the evaporator, to match the<br />
compressor capacity. This provides for increased part load efficiencies compared<br />
to a fixed orifice device.<br />
There are two types of sensors that are used on <strong>RTAC</strong> <strong>and</strong> <strong>RTHD</strong> units. A float<br />
type senor with an external LLID was originally used on <strong>RTAC</strong> <strong>and</strong> <strong>RTHD</strong> units. A<br />
capacitance based with an internal LLID will soon be used on all units.<br />
The sensor consists of a body made from an enclosed tube <strong>and</strong> fitting, <strong>and</strong> a<br />
magnetic float which slides over the tube. Internal to the tube, <strong>and</strong> isolated from<br />
the refrigerant, is a narrow PC board with a resistor <strong>and</strong> magnetic reed switch<br />
array. The float's magnets close the reed switches pattern as it moves up the<br />
tube, creating a changing resistance (<strong>and</strong> ultimately a direct acting DC output<br />
voltage) similar to that of a potentiometer<br />
This new level sensor is a capacitive based switch. This switch is more reliable<br />
<strong>and</strong> has no moving parts. It is less sensitive to foam <strong>and</strong> will provide consistent<br />
operation across the operating map.This new sensor can be installed on existing<br />
chillers using an adapter.<br />
There are 2 capacitor sensors in the copper tube. The lower sensor is used to<br />
determine the capacitance of the liquid (refrigerant <strong>and</strong> oil mixture). The upper<br />
sensor is used to determine the height of the liquid in the evaporator.<br />
Liquid Level Sensor Checkout Procedure<br />
Is the sensor<br />
bound <strong>and</strong><br />
communicating?<br />
Liquid Level Sensor<br />
Connect TechView <strong>and</strong> get into Binding View. This will shut the chiller down.<br />
Once in Binding View verify that the Liquid Level Senor is bound.<br />
Note: Please refer to Service Tool for questions concerning binding LLIDs <strong>and</strong><br />
getting into Binding View.<br />
If there are multiple LLIDs that are not verified go to IPC troubleshooting.<br />
If the sensor is not bound, try to bind it. If the sensor will not bind, it could be a<br />
problem with the connector or the sensor itself. Take a close look at the<br />
connector to make sure that all four wires are securely in place. It may be<br />
necessary to remove the cap to check for broken or misplaced wires.<br />