External LLID Sensor<br />

Internal LLID<br />

The liquid level sensor is mounted in a small tank or canister attached to the<br />

outside of the tube sheet. The evaporator’s liquid level is transmitted into the<br />

tank through a small vapor <strong>and</strong> liquid line.<br />

The liquid level sensor is required to provide input for control of the EXV, which<br />

allows the regulation of refrigerant flow into the evaporator, to match the<br />

compressor capacity. This provides for increased part load efficiencies compared<br />

to a fixed orifice device.<br />

There are two types of sensors that are used on <strong>RTAC</strong> <strong>and</strong> <strong>RTHD</strong> units. A float<br />

type senor with an external LLID was originally used on <strong>RTAC</strong> <strong>and</strong> <strong>RTHD</strong> units. A<br />

capacitance based with an internal LLID will soon be used on all units.<br />

The sensor consists of a body made from an enclosed tube <strong>and</strong> fitting, <strong>and</strong> a<br />

magnetic float which slides over the tube. Internal to the tube, <strong>and</strong> isolated from<br />

the refrigerant, is a narrow PC board with a resistor <strong>and</strong> magnetic reed switch<br />

array. The float's magnets close the reed switches pattern as it moves up the<br />

tube, creating a changing resistance (<strong>and</strong> ultimately a direct acting DC output<br />

voltage) similar to that of a potentiometer<br />

This new level sensor is a capacitive based switch. This switch is more reliable<br />

<strong>and</strong> has no moving parts. It is less sensitive to foam <strong>and</strong> will provide consistent<br />

operation across the operating map.This new sensor can be installed on existing<br />

chillers using an adapter.<br />

There are 2 capacitor sensors in the copper tube. The lower sensor is used to<br />

determine the capacitance of the liquid (refrigerant <strong>and</strong> oil mixture). The upper<br />

sensor is used to determine the height of the liquid in the evaporator.<br />

Liquid Level Sensor Checkout Procedure<br />

Is the sensor<br />

bound <strong>and</strong><br />

communicating?<br />

Liquid Level Sensor<br />

Connect TechView <strong>and</strong> get into Binding View. This will shut the chiller down.<br />

Once in Binding View verify that the Liquid Level Senor is bound.<br />

Note: Please refer to Service Tool for questions concerning binding LLIDs <strong>and</strong><br />

getting into Binding View.<br />

If there are multiple LLIDs that are not verified go to IPC troubleshooting.<br />

If the sensor is not bound, try to bind it. If the sensor will not bind, it could be a<br />

problem with the connector or the sensor itself. Take a close look at the<br />

connector to make sure that all four wires are securely in place. It may be<br />

necessary to remove the cap to check for broken or misplaced wires.<br />

RLC-SVD05A-EN 57