17.12.2012 Views

RTHD and RTAC - Trane

RTHD and RTAC - Trane

RTHD and RTAC - Trane

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

Current Transformers<br />

Each compressor motor has all three of its line currents monitored by toroid<br />

(doughnut) current transformers. These currents are normalized with respect to<br />

the Rated Load Amps of the respective compressor <strong>and</strong> thus are expressed in<br />

terms of % RLA <strong>and</strong> in Amps. The currents are “normalized” through the proper<br />

selection of the Current Transformer <strong>and</strong> the unit configuration. CTs are selected<br />

based on the motor RLA. Refer to Table 5.<br />

The current transformers provide the input for five basic functions of the starter<br />

module:<br />

1 Current overload protection using a programmed % of Rated Load Amps<br />

versus time to trip characteristic. The steady state “must trip” value is 140%<br />

RLA <strong>and</strong> the “must hold” value is 125% RLA. The starter Module will trip out<br />

the compressor, <strong>and</strong> the Main Processor (MP) will then shut down the other<br />

compressor on the same refrigerant circuit (if applicable). The appropriate<br />

diagnostic codes will be displayed.<br />

2 Loss of Phase Current. A phase loss due specifically to lack of Current<br />

Transformer inputs is not looked for during transition (which lasts for 3<br />

seconds in software) <strong>and</strong> is additionally delayed 2.8 seconds. As such, the<br />

diagnostic will not be called out any sooner than 5.8 seconds after transition<br />

even if it occurs immediately at start. Additional, two of the three current<br />

inputs also serve the Phase Rotation circuits. If this circuit (monitored<br />

immediately after start), outputs an inconsistent value to the module (due to<br />

loss of one or both of its inputs), a diagnostic of either Phase Loss (steady<br />

output) or Phase Reversal Protection Lost (varying output) will occur with a<br />

maximum delay of 1.2 seconds after start.<br />

3 Phase Rotation. Screw compressors cannot be allowed to run in reverse<br />

direction. To protect the compressors, the phase rotation is detected by the<br />

current transformers immediately at start up. If improper phasing is detected,<br />

within 1 second of startup, the Starter Module will trip out the compressor,<br />

<strong>and</strong> the MP will then shut down the other compressor on the same refrigerant<br />

circuit (if applicable). The Phase Rotation diagnostic codes will be displayed.<br />

Phase Rotation is only active for the first second of operation.<br />

4 Phase Unbalance. The Starter Module will shut down the compressor if a<br />

phase current unbalance is detected by the current transformers while the<br />

compressor is running. A 30% unbalance will cause the Starter Module to trip<br />

out the compressor, <strong>and</strong> the MP will then shut down the other compressor on<br />

the same refrigeration circuit (if applicable). Phase unbalance is based on the<br />

following calculation:<br />

% unbalance = (I0x-Iave) x 100<br />

26 RLC-SVD05A-EN<br />

Iave

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!