RTHD and RTAC - Trane
RTHD and RTAC - Trane
RTHD and RTAC - Trane
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
Over/Under Voltage<br />
Starter Module 1 Switch the line power off <strong>and</strong> run a separate 120 VAC control power to the<br />
chiller controls. With the controls powered up (Chiller mode set to Stop),<br />
measure the common mode input voltages to the Starter module as VDC <strong>and</strong><br />
verify they fall within the following:<br />
Table 7. Starter Module Potential Transformer Input DC Voltages<br />
Starter Module Input Minimum Acceptable DC Maximum Acceptable DC<br />
Terminals<br />
Voltage(VDC)<br />
Voltage(VDC)<br />
J5-1 with respect to ground +2.45 +2.55<br />
J5-2 with respect to ground +2.45 +2.55<br />
J5-3 with respect to ground +2.45 +2.55<br />
J5-4 with respect to ground +2.45 +2.55<br />
J5-5 with respect to ground +2.45 +2.55<br />
J5-6 with respect to ground +2.45 +2.55<br />
2 If any of the voltages are not within the acceptable range listed in Appendix A<br />
Table 2, then disconnect all the external wires to the J5-1 to 6 terminals. Again<br />
measure the voltages in Table 7..<br />
If the voltages all fall within the acceptable range, then there is most likely an<br />
error in the external wiring to the Starter module potential transformer inputs.<br />
This includes the potential transformers themselves.<br />
If any voltage is not within the acceptable range, then there is most likely a<br />
problem with installation of the Starter module or with the Starter module<br />
itself. Check the four wire LLIDs bus connection to the Starter module. Check<br />
the 24 +/- 2.4 VDC power supply input. Insure the Starter module is grounded<br />
via the mounting screws. If installation is correct, replace the Starter module.<br />
RLC-SVD05A-EN 33