Starter<br />

Solid State - <strong>RTHD</strong> Only<br />

CH530 provides an interface with Non-Communicating Solid State Starter.<br />

The following points of interface are provided.<br />

Start contact closure output: This contact closure output will be closed when the<br />

compressor motor is to run <strong>and</strong> opened when the compressor motor is not to<br />

run. This output will be latched to prevent chatter of this comm<strong>and</strong> to the starter<br />

Up To Speed contact closure input: This contact closure input is closed when<br />

the solid state starter has started <strong>and</strong> accelerated the compressor motor. Failure<br />

of this input to close within the maximum acceleration time will cause the "Motor<br />

Failed to Accelerate" diagnostic to be called out.<br />

Starter Fault contact closure input: This high voltage binary input will be open<br />

when the solid state starter system is not powered <strong>and</strong> when the solid state<br />

starter has an active fault. It will be high voltage (115 VAC) during normal<br />

operation of the solid state starter. This input shall be ignored for five seconds<br />

following power-up. After the first five seconds, if this input voltage is high, a<br />

Starter Fault diagnostic shall be called out.<br />

The sequence of a Solid State Start is shown in Figure 29<br />

Refer to <strong>RTHD</strong>-SVD01A-EN for IT Solid State Starter Troubleshooting.<br />

Refer to <strong>RTHD</strong>-SVD02A-EN for RediStart Solid State Starter Troubleshooting.<br />

<strong>RTHD</strong> Sequence of Operation:<br />

Starting Non-Communicating Solid State Starter<br />

Waiting<br />

To Start<br />

Check for At Speed Input Opened<br />

(1 Second)<br />

Energize Stop <strong>and</strong> Start<br />

Relays<br />

Confirm Individual Phase<br />

Currents are > 10% RLA<br />

within 2.6 seconds<br />

Accelerating<br />

Compressor<br />

(6 to 64 Seconds (Default 7 sec))<br />

Starting Compressor<br />

Run Comm<strong>and</strong> to Starter Module<br />

Figure 29.<strong>RTHD</strong> Sequence of Operation Solid State Start<br />

Confirm At Speed Input within<br />

Maximum Acceleration Timer<br />

(Default 7 seconds)<br />

Running<br />

Running<br />

RLC-SVD05A-EN 43