GeneralitiesSafety of people<br />

PE50798 61058N<br />

61012N<br />

DE53514<br />

PE57841<br />

SF1 circuit breaker<br />

Evolis circuit breaker<br />

Evolis lateral version<br />

Vacuum type contactor<br />

AMTED398078EN.indd<br />

By switchgear<br />

SF6 circuit breaker: SF1<br />

b Gas tightness<br />

The SF1 circuit breaker is made up of three separate poles mounted<br />

on a structure supporting the operating mechanism. Each pole-unit houses<br />

all the active elements in an insulating enclosure fi lled with gas to a relative pressure<br />

of 0.5 bar (500 hPa) for 24 kV and 2 bar (2000 hPa) for 36 kV. It satisfi es “sealed<br />

pressure system” requirements and seal tightness is always checked in the factory.<br />

b Operating safety<br />

Accidental over-pressures are eliminated by the opening of the safety membrane.<br />

Contacts closed Precompression Arcing period Contacts open<br />

Vacuum type circuit breaker: Evolis<br />

b Vacuum tightness<br />

The Evolis circuit breaker comprises three separate pole <strong>units</strong> fi xed on a structure<br />

supporting the control mechanism. Each pole encloses all of the active parts in an<br />

insulating enclosure, under vacuum, and its vacuum tightness is systematically<br />

checked in the factory.<br />

b Operating safety<br />

The magnetic fi eld is applied along the contact axis of the vacuum type circuit breaker.<br />

This process diffuses the arc in a regular manner with high currents.<br />

It ensures optimum distribution of the energy along the compact surface<br />

so as to avoid local hot spots.<br />

The advantages of this technique:<br />

v a simplifi ed vacuum type circuit breaker which is consequently very reliable,<br />

v low dissipation of arcing energy in the circuit breaker,<br />

v highly effi cient contacts which do not distort during repeated breaking,<br />

v signifi cant reduction in control energy.<br />

Vacuum type contactor<br />

b Vacuum tightness<br />

Vacuum contactor comprises three separate poles fi xed on a structure supporting<br />

the control mechanism. Each pole encloses all of the active parts in an insulating<br />

enclosure under vacuum and its vacuum tightness is checked in the factory.<br />