DE58402<br />
Generalities Description of the control/<br />
monitoring & protection functions<br />
CRa, CRb, CRc current sensor<br />
Current sensor for VIP 35 and VIP 300LL<br />
and Sepam series 10 for 24 kV<br />
Type Dimensions (mm) Weight Ratio of Class of precision VIP 35 VIP 300LL Sepam 10<br />
External Internal Thickness (kg) transformation<br />
Ø Ø (without<br />
fastening)<br />
CRa 143.5 81 37.5 2.18 1/200 ± 2% from 10 A to 100 A<br />
± 1% from 100 A to 1600 A<br />
On load 5.7 Ω (cal. x 1) b b<br />
± 1% from 10 A to 10 kA On load 0.67 Ω (cal. x 4)<br />
CRb 143.5 81 37.5 1.26 1/1250 ± 1% from 10 A to 11 kA On load 5.7 Ω (cal. x 1) b b<br />
± 1 % from 10 A to 25 kA On load 0.67 Ω (cal. x 4)<br />
CRc 143.5 81 37.5 2 S1-S2: 1/200 S1-S2:<br />
± 5% from 10 A to 80 A<br />
± 2.5 % from 80 A to 600 A<br />
On load 0.6 Ω b<br />
S1-S3: 1/500 S1-S3:<br />
± 2% from 20 A to 2200 A<br />
General common selection of protection <strong>units</strong><br />
Protection type Code Protection <strong>units</strong><br />
Sepam VIP<br />
series 10 series 20 series 40 series 80 35 300<br />
Three-phase overcurrent 50 - 51 b b b b b (2) b (1)<br />
Zero-sequence overcurrent 50N - 51N b b b b b (3) b (1)<br />
Directional zero-sequence current 67N b b<br />
Undervoltage 27 b b<br />
Overvoltage 59 b b<br />
Thermal image 49 b b b b<br />
Zero-sequence overvoltage 59N b b<br />
Negative sequence overcurrent 46 b b b<br />
Long start-up and rotor blocking 51LR b b b<br />
Maximum number of start-ups 66 b b b<br />
Single-phase undercurrent 37 b b b<br />
Communication b b b b<br />
(1) DT, EI, SI, VI and RI trip curves.<br />
(2) Inverse curve suited to transformer protection.<br />
(3) DT trip curve.<br />
40 AMTED398078EN.indd