DE59704<br />

DE59709<br />

Characteristics of<br />

the functional <strong>units</strong><br />

SM<br />

Disconnector unit<br />

Electrical characteristics<br />

kA Ik/1s<br />

25<br />

20<br />

16<br />

12.5<br />

AMTED398078EN.indd<br />

Ir = 630 - 1250 A<br />

Ir = 400 - 630 - 1250 A<br />

7.2 12 17.5 24 36<br />

Basic equipment:<br />

b disconnector and earthing switch<br />

b three-phase busbars<br />

b operating mechanism CS<br />

b 150 W heating element for 36 kV<br />

Ir =<br />

1250 A<br />

b connection pads for dry-type cables<br />

b voltage presence indicator<br />

Ur<br />

kV<br />

DE53557<br />

DE59718<br />

Functional <strong>units</strong> selection<br />

Other functions<br />

TM<br />

MV/LV transformer unit<br />

for auxiliaries<br />

kA Ik/1s<br />

25<br />

20<br />

16<br />

12.5<br />

Ir = 50 A<br />

7.2 12 17.5 24 36<br />

kV<br />

b two 6.3 A fuses, UTE (for 24 kV)<br />

or DIN type<br />

b LV circuit isolating switch<br />

b one voltage transformer (phase-to-phase)<br />

Optional accessories:<br />

b auxiliary contacts<br />

b key-type interlocks<br />

b 1250 A three-phase upper busbars at Ir 630 A<br />

b cable connection by the top for 24 kV (no internal arc withstand if selected)<br />

b enlarged low-voltage control cabinet for 24 kV<br />

b 50 W heating element for 24 kV<br />

b 630 A three-phase upper busbars for severe operating conditions for 24 kV<br />

b digital ammeter for 24 kV<br />

b mechanical indication system and<br />

auxiliary contacts for blown fuses<br />

Ur<br />

DE53558<br />

DE59212<br />

EMB<br />

Busbars earthing<br />

compartment unit<br />

kA Ik/1s<br />

25<br />

20<br />

16<br />

12.5<br />

Ir = 630 A<br />

Ir = 400 - 630 A<br />

7.2 12 17.5 24<br />

Ur<br />

kV<br />

b earthing switch<br />

b connection bars<br />

b operating mechanism CIT<br />

b installation on 630 A IM 375 mm or<br />

DM1-A <strong>units</strong> (except additional<br />

enclosure or connection enclosure<br />

for cabling from above)<br />

b require an key-type interlocks<br />

adapted to the switchboard network<br />

b auxiliary contacts<br />

59