Generalities LPCT protection chain<br />

TLP130, CLP2 sensors and<br />

Sepam series 20, series 40, series 80<br />

protection <strong>units</strong><br />

Standard<br />

applications<br />

Sepam series 20<br />

Demanding<br />

applications<br />

Sepam series 40<br />

Custom<br />

applications<br />

Sepam series 80<br />

AMTED398078EN.indd<br />

DE58405EN<br />

LPCT sensors are voltage-output current sensors (Low Power Current<br />

Transformer) compliant with the IEC 60044-8 standard.<br />

These sensors are designed to measure rated current between 5 A and 630 A,<br />

with a ratio of 100 A / 22.5 mV.<br />

Sepam series 20, series 40, series 80 protection <strong>units</strong> are at the heart<br />

of the LPCT protection chain.<br />

Sepam series 20, series 40, series 80 performs the following functions:<br />

b acquisition of phase currents measured by the LPCT sensors<br />

b utilization of measurements by the protection functions<br />

b tripping of the breaking device in case of fault detection.<br />

Advantages<br />

b Consistent protection chain with the same sensor measures phase currents<br />

from 5 A to 630 A<br />

b Simple to install and implement:<br />

v installation of LPCT sensors<br />

- TLP130, TLP160 and TLP190 are installed around MV cable<br />

- CLP2 is installed on the MV circuit<br />

v LPCT connected directly to Sepam series 20, series 40, series 80<br />

v accessories available to test the LPCT protection chain by secondary current<br />

injection.<br />

b LPCTs range of use<br />

LPCT measuring and protection function guaranteeing the accuracy up to<br />

the short-time current.<br />

Following the range of use of LPCT:<br />

v from 5 A up to 1250 A respecting the error limits imposed by the accuracy class 0,5<br />

v from 1250 A up to 50 kA respecting the error limits imposed by the accuracy class 5P.<br />

5.00<br />

4.75<br />

4.50<br />

4.25<br />

4.00<br />

3.75<br />

3.50<br />

3.25<br />

3.00<br />

2.75<br />

2.50<br />

2.25<br />

2.00<br />

1.75<br />

1.50<br />

1.25<br />

1.00<br />

0.75<br />

0.50<br />

0.25<br />

Ratio error<br />

Protective class 5P<br />

Measuring class 0.5<br />

5 20 100 1000 1250 2000 3000 31500 40000 50000<br />

b Optimized integration of functions:<br />

v measurement of phase rated currents as of 25 A that is set by micro-switch<br />

v monitoring of LPCT sensor by Sepam series 20, series 40, series 80 (detection of<br />

phase loss).<br />

Connections<br />

1 LPCT sensor, equipped with a shielded cable fi tted with an RJ45 connector<br />

to be connected directly to the card 3<br />

2 Sepam series 20, series 40, series 80 protection unit<br />

3 Card interface that adapts the voltage delivered by the LPCT sensors,<br />

with microswitch setting of rated current.<br />

v CCA671 card for series 80<br />

v CCA670 card for series 20 and 40.<br />

Testing and injection<br />

4 CCA613 remote test plug, fl ush-mounted in front panel of cubicle, equipped<br />

with a 3-m cord to be connected to the CCA670 connector test socket (9-pin Sub D)<br />

5 ACE917 injection interface, used to test the LPCT protection chain with<br />

a standard injection box<br />

6 Standard 1A injection box.<br />