Generalities LPCT protection chain<br />
TLP130, CLP2 sensors and<br />
Sepam series 20, series 40, series 80<br />
protection <strong>units</strong><br />
Standard<br />
applications<br />
Sepam series 20<br />
Demanding<br />
applications<br />
Sepam series 40<br />
Custom<br />
applications<br />
Sepam series 80<br />
AMTED398078EN.indd<br />
DE58405EN<br />
LPCT sensors are voltage-output current sensors (Low Power Current<br />
Transformer) compliant with the IEC 60044-8 standard.<br />
These sensors are designed to measure rated current between 5 A and 630 A,<br />
with a ratio of 100 A / 22.5 mV.<br />
Sepam series 20, series 40, series 80 protection <strong>units</strong> are at the heart<br />
of the LPCT protection chain.<br />
Sepam series 20, series 40, series 80 performs the following functions:<br />
b acquisition of phase currents measured by the LPCT sensors<br />
b utilization of measurements by the protection functions<br />
b tripping of the breaking device in case of fault detection.<br />
Advantages<br />
b Consistent protection chain with the same sensor measures phase currents<br />
from 5 A to 630 A<br />
b Simple to install and implement:<br />
v installation of LPCT sensors<br />
- TLP130, TLP160 and TLP190 are installed around MV cable<br />
- CLP2 is installed on the MV circuit<br />
v LPCT connected directly to Sepam series 20, series 40, series 80<br />
v accessories available to test the LPCT protection chain by secondary current<br />
injection.<br />
b LPCTs range of use<br />
LPCT measuring and protection function guaranteeing the accuracy up to<br />
the short-time current.<br />
Following the range of use of LPCT:<br />
v from 5 A up to 1250 A respecting the error limits imposed by the accuracy class 0,5<br />
v from 1250 A up to 50 kA respecting the error limits imposed by the accuracy class 5P.<br />
5.00<br />
4.75<br />
4.50<br />
4.25<br />
4.00<br />
3.75<br />
3.50<br />
3.25<br />
3.00<br />
2.75<br />
2.50<br />
2.25<br />
2.00<br />
1.75<br />
1.50<br />
1.25<br />
1.00<br />
0.75<br />
0.50<br />
0.25<br />
Ratio error<br />
Protective class 5P<br />
Measuring class 0.5<br />
5 20 100 1000 1250 2000 3000 31500 40000 50000<br />
b Optimized integration of functions:<br />
v measurement of phase rated currents as of 25 A that is set by micro-switch<br />
v monitoring of LPCT sensor by Sepam series 20, series 40, series 80 (detection of<br />
phase loss).<br />
Connections<br />
1 LPCT sensor, equipped with a shielded cable fi tted with an RJ45 connector<br />
to be connected directly to the card 3<br />
2 Sepam series 20, series 40, series 80 protection unit<br />
3 Card interface that adapts the voltage delivered by the LPCT sensors,<br />
with microswitch setting of rated current.<br />
v CCA671 card for series 80<br />
v CCA670 card for series 20 and 40.<br />
Testing and injection<br />
4 CCA613 remote test plug, fl ush-mounted in front panel of cubicle, equipped<br />
with a 3-m cord to be connected to the CCA670 connector test socket (9-pin Sub D)<br />
5 ACE917 injection interface, used to test the LPCT protection chain with<br />
a standard injection box<br />
6 Standard 1A injection box.<br />