Modular units
Modular units
Modular units
You also want an ePaper? Increase the reach of your titles
YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.
PE55648 61046N<br />
61045N<br />
Characteristics of<br />
the functional <strong>units</strong><br />
Voltage transformers for 24 kV<br />
Synthesis table by unit<br />
Units CM CVM DM1-A DM1-D<br />
DMVL-D<br />
DM1-W DM2 GBC-A GBC-B DMVL-A DMV-A DMV-D CM2 TM<br />
VTs<br />
VRQ2-n/S1 b b b b b b b b<br />
VRFR-n/S1 b b b<br />
VRC2/S1 b b b<br />
VRM3-n/S2 b b<br />
VCT24<br />
b<br />
VRC1/S1<br />
b<br />
Transformer VRQ2-n/S1 (phase-to-earth) 50 or 60 Hz<br />
b characteristics according to IEC standard 60044-2.<br />
Rated voltage (kV) 24<br />
Primary voltage (kV) 10/3 15/3 15-20/3 20/3<br />
Secondary voltage (V) 100/3<br />
Thermal power (VA) 250<br />
Accuracy class 0.5<br />
Rated output for<br />
single primary winding (VA)<br />
30 30 30<br />
Rated output for<br />
double primary winding (VA)<br />
30-50<br />
Transformer VRFR-n/S1 (phase-to-earth) 50 or 60 Hz<br />
b characteristics according to IEC standard 60044-2.<br />
Rated voltage (kV) 17.5<br />
Primary voltage (kV) 10/3 15/3<br />
Secondary voltage (V) 100/3<br />
Thermal power (VA) 250<br />
Accuracy class 0.5<br />
Rated output for<br />
single primary winding (VA)<br />
30<br />
Transformer VRC2/S1 (phase-to-phase) 50 or 60 Hz<br />
b characteristics according to IEC standard 60044-2.<br />
Rated voltage (kV) 24<br />
Primary voltage (kV) 10 15 20<br />
Secondary voltage (V) 100<br />
Thermal power (VA) 500<br />
Accuracy class 0.5<br />
Rated output for<br />
single primary winding (VA)<br />
50<br />
Transformer VRM3-n/S2 (phase-to-earth and protected by fuses 0.3 A) 50 or 60 Hz<br />
b characteristics according to IEC standard 60044-2.<br />
Rated voltage (kV) 12 17.5 24<br />
Primary voltage (kV) 10/3 15/3 20/3<br />
Secondary voltage (V) 100/3 - 100/3<br />
First secondary Thermal power (VA) 200<br />
Accuracy class 0.5<br />
Rated output for single primary (VA) 30-50<br />
Second secondary Thermal power (VA) 100<br />
Accuracy class 3P<br />
Rated output 50<br />
74 AMTED398078EN.indd