PE55648 61046N<br />

61045N<br />

Characteristics of<br />

the functional <strong>units</strong><br />

Voltage transformers for 24 kV<br />

Synthesis table by unit<br />

Units CM CVM DM1-A DM1-D<br />

DMVL-D<br />

DM1-W DM2 GBC-A GBC-B DMVL-A DMV-A DMV-D CM2 TM<br />

VTs<br />

VRQ2-n/S1 b b b b b b b b<br />

VRFR-n/S1 b b b<br />

VRC2/S1 b b b<br />

VRM3-n/S2 b b<br />

VCT24<br />

b<br />

VRC1/S1<br />

b<br />

Transformer VRQ2-n/S1 (phase-to-earth) 50 or 60 Hz<br />

b characteristics according to IEC standard 60044-2.<br />

Rated voltage (kV) 24<br />

Primary voltage (kV) 10/3 15/3 15-20/3 20/3<br />

Secondary voltage (V) 100/3<br />

Thermal power (VA) 250<br />

Accuracy class 0.5<br />

Rated output for<br />

single primary winding (VA)<br />

30 30 30<br />

Rated output for<br />

double primary winding (VA)<br />

30-50<br />

Transformer VRFR-n/S1 (phase-to-earth) 50 or 60 Hz<br />

b characteristics according to IEC standard 60044-2.<br />

Rated voltage (kV) 17.5<br />

Primary voltage (kV) 10/3 15/3<br />

Secondary voltage (V) 100/3<br />

Thermal power (VA) 250<br />

Accuracy class 0.5<br />

Rated output for<br />

single primary winding (VA)<br />

30<br />

Transformer VRC2/S1 (phase-to-phase) 50 or 60 Hz<br />

b characteristics according to IEC standard 60044-2.<br />

Rated voltage (kV) 24<br />

Primary voltage (kV) 10 15 20<br />

Secondary voltage (V) 100<br />

Thermal power (VA) 500<br />

Accuracy class 0.5<br />

Rated output for<br />

single primary winding (VA)<br />

50<br />

Transformer VRM3-n/S2 (phase-to-earth and protected by fuses 0.3 A) 50 or 60 Hz<br />

b characteristics according to IEC standard 60044-2.<br />

Rated voltage (kV) 12 17.5 24<br />

Primary voltage (kV) 10/3 15/3 20/3<br />

Secondary voltage (V) 100/3 - 100/3<br />

First secondary Thermal power (VA) 200<br />

Accuracy class 0.5<br />

Rated output for single primary (VA) 30-50<br />

Second secondary Thermal power (VA) 100<br />

Accuracy class 3P<br />

Rated output 50<br />

74 AMTED398078EN.indd