Modular units
Modular units
Modular units
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
PE57159<br />
PE57160<br />
Generalities Description of the control/<br />
monitoring & protection functions<br />
VIP 35<br />
Setting values of the Is phase operating current for VIP 35<br />
VIP 300 LL<br />
VIP 35 relay for transformer protection<br />
Integrated in the DM1-S and DMV-S cubicles for SM6 24 kV<br />
The VIP 35 is an independent relay without an auxiliary power supply, powered<br />
by the current sensors, and actuating a Mitop release unit.<br />
VIP 35 provides protection against phase-to-phase faults and against earthing faults.<br />
Phase protection<br />
b phase protection is achieved by a defi nite time threshold which functions<br />
from 1.2 times the operating current (Is).<br />
Earthing protection<br />
b earthing fault protection functions with the residual current measurement taken<br />
from the sum of the secondary currents in the sensors. This is taken via a CRc,<br />
8 A to 80 A gauge.<br />
b earthing protection is inverse defi nite time: its threshold and time delay can be set.<br />
Setting the VIP 35 relays<br />
Is: the phase operating current is adjusted directly in accordance with the transformer<br />
rating and the operating voltage.<br />
Io: the earth current threshold is adjusted according to the network characteristics.<br />
Operating Transformer rating (kVA)<br />
voltage (kV) 50 75 100 125 160 200 250 315 400 500 630 800 1000 1250 1600 2000 2500 3150 4000 5000 6300<br />
3 10 15 20 25 36 45 55 68 80 115 140 170 200<br />
3.3 10 15 18 22 28 36 45 56 70 90 115 140 200<br />
4.2 8 12 15 18 22 28 36 45 55 70 90 115 140 200<br />
5.5 8* 8 12 15 18 22 28 36 45 55 68 90 115 140 170<br />
6 8* 8* 10 12 18 20 25 36 45 55 68 80 115 140 170 200<br />
6.6 8* 8* 10 12 15 18 22 28 36 45 56 70 90 115 140 200<br />
10 8* 8* 8* 8 10 12 15 20 25 30 37 55 68 80 115 140 170 200<br />
11 8* 8* 8* 8* 10 12 15 18 22 28 36 45 55 68 90 115 140 170<br />
13.8 8* 8* 8* 8* 8 10 12 15 18 22 28 36 45 55 68 90 115 140 170<br />
15 8* 8* 8* 8* 8* 8 10 15 18 20 25 36 45 55 68 80 115 140 170 200<br />
20 8* 8* 8* 8* 8* 8* 8 10 12 15 20 25 30 37 55 68 80 115 140 170 200<br />
22 8* 8* 8* 8* 8* 8* 8 10 12 15 18 22 28 36 45 55 68 90 115 140 170<br />
* Short-circuit protection, no over-load protection<br />
VIP 300 LL protection relay<br />
Integrated in the DM1-S and DMV-S cubicles for SM6 24 kV<br />
VIP 300 provides protection against phase-to-phase and phase-to-earth faults.<br />
A choice of trip curves and the large number of possible settings mean that it can be<br />
used in a large variety of selectivity layouts.<br />
VIP 300 is an independent relay powered by the current sensors; it does not require<br />
an auxiliary power supply. It actuates a release unit.<br />
Phase protection<br />
b phase protection is via two independently adjustable thresholds:<br />
v the lower threshold can be chosen to be inverse defi nite time or defi nite time.<br />
The defi nite time curves are in conformity with IEC standard 60255-3.<br />
They are either of inverse, very inverse or extremely inverse type.<br />
v the upper threshold is inverse defi nite time.<br />
Earthing protection<br />
b protection against phase-to-earth faults uses the residual current measurement,<br />
taken from the sum of the secondary currents in the sensors. This is taken via<br />
a CRa X1 gauge: 10 to 50 A and X4: 40 to 200 A or via a CRb X1 gauge:<br />
63 to 312 A and X4: 250 A to 1250 A.<br />
b as for phase protection, phase-to-earth protection had two thresholds<br />
that can be independently set.<br />
Signalling<br />
b two indicators show the origin of the trip operation (phase or earth).<br />
They remain in position after the relay power supply has been cut.<br />
two led indicators (phase and earth) show that the lower threshold<br />
has been exceeded and that its time delay is currently in progress.<br />
38 AMTED398078EN.indd