DE53562 DE52402<br />
DE58408<br />
Characteristics of<br />
the functional <strong>units</strong><br />
AMTED398078EN.indd<br />
Voltage transformers for 24 kV<br />
Transformer VRC1/S1 (phase-to-phase) 50 or 60 Hz<br />
b characteristics according to IEC standard 60044-2.<br />
Rated voltage (kV) 7.2<br />
Primary voltage (kV) 3.3 5 5.5 6 6.6<br />
Secondary voltage (V) 110 100 110 100 110<br />
Thermal power (VA) 300<br />
Accuracy class 0.5<br />
Rated output for<br />
single primary winding (VA)<br />
100<br />
Transformer VCT24 (phase-to-phase) 50 or 60 Hz<br />
Rated voltage (kV) 24<br />
Primary voltage (kV) 10 15 20<br />
Secondary voltage (V) 220<br />
Output (VA) 2500 2500 2500<br />
4000 4000<br />
Note: the above mentioned voltage transformers are grounded neutral.<br />
For other characteristics, please consult us.<br />
Surge arresters<br />
For <strong>units</strong> IM500, DM1-A, DM1-W, GAM, DMV-A*, DMVL-A<br />
In (A) 400/630<br />
Un (kV) 7.2 10 12 17.5 24<br />
Note: the rated voltage of the surge arrester is according to unit’s rated voltage.<br />
(*) limited up to 17.5 kV for DMV-A circuit breaker cubicles.<br />