Modular units
Modular units
Modular units
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
DE53585<br />
DE53586<br />
Connections Cable-connection from below<br />
for 24 kV<br />
Trenches depth<br />
625<br />
500<br />
375<br />
187.5<br />
Cabling from below (all <strong>units</strong>)<br />
b Through trenches: the trench depth P is given in the table opposite for commonly<br />
used dry single-core cables type (for tri-core cables consult us).<br />
b With stands: to reduce P or eliminate trenches altogether by placing the <strong>units</strong><br />
on 400 mm concrete footings.<br />
b With fl oor void: the trench depth P is given in the table opposite for commonly<br />
used types of cables.<br />
Single-core cables Units until 630 A 1250 A <strong>units</strong><br />
Cable<br />
x-section<br />
(mm 2 )<br />
Bending<br />
radius<br />
(mm)<br />
IM,<br />
SM,<br />
NSM-cables,<br />
NSM-busbars<br />
IMC, DM1-A,<br />
DM1-W,<br />
DM1-S,<br />
DMVL-A,<br />
GAM<br />
86 AMTED398078EN.indd<br />
CRM<br />
CVM<br />
DMV-A,<br />
DMV-S<br />
PM,<br />
QM,<br />
QMC (1)<br />
SM,<br />
GAM<br />
DM1-A (2)<br />
DM1-W (2)<br />
DMV-A (3)<br />
Depth P (mm) all orientations<br />
P1 P2 P2 P2 P3 P4 P5 P6<br />
50 370 140 400 400 500 350<br />
70 400 150 430 430 530 350<br />
95 440 160 470 470 570 350<br />
120 470 200 500 500 600<br />
150 500 220 550 650<br />
185 540 270 670 770<br />
240 590 330 730 830<br />
400 800 1000 1350 1450<br />
630 940 1000 1350 1450<br />
(1) Must be installed with a 100 mm depth metal pan.<br />
(2) Must be installed with a 350 mm depth metal pan, in a fl oor void.<br />
(3) Mounting with a 445 mm depth metal pan compulsory in a fl oor void.<br />
Note: the unit and the cables requiring the greatest depth must be taken into account<br />
when determining the depth P or single-trench installations.<br />
In double-trench installations, depth P must be taken into account for each type of unit<br />
and cable orientations.<br />
Cable trench drawings<br />
1250 A <strong>units</strong> (represented without switchboard side panels) 630 A <strong>units</strong><br />
SM, GAM<br />
For single and tri-core cables<br />
140<br />
50<br />
740<br />
600<br />
P4<br />
DE53587<br />
DMV-A<br />
For single and tri-core cables<br />
140<br />
50<br />
740<br />
600<br />
480<br />
445<br />
P6<br />
DE58350<br />
DM1-A, DM1-W<br />
For single-core cables<br />
140<br />
80<br />
50<br />
740<br />
840<br />
P5<br />
DE53589<br />
DMV-A, DMV-S<br />
For single cables<br />
140<br />
50<br />
740<br />
600<br />
100<br />
P2