DE53527<br />

DE59220<br />

Characteristics of<br />

the functional <strong>units</strong><br />

CVM<br />

Disconnectable contactor unit<br />

Electrical characteristics<br />

kA Ik/1s & Isc<br />

10<br />

8<br />

6.3<br />

Ir = 400 A<br />

7.2<br />

AMTED398078EN.indd<br />

12<br />

Ur<br />

kV<br />

DE53528<br />

DE59221<br />

Functional <strong>units</strong> selection<br />

Contactor protection<br />

CVM<br />

Disconnectable contactor unit with fuses<br />

kA Isc<br />

Ir = 250 A<br />

7.2 12<br />

Basic equipment:<br />

b vacuum contactor<br />

b disconnector and earthing switch<br />

b three-phase busbars<br />

b contactor operating mechanism with magnetic holding or contactor with mechanical latching<br />

b disconnector operating mechanism CS<br />

b one to three current transformers<br />

b auxiliary contacts on contactor<br />

b connection pads for dry-type cables<br />

b voltage presence indicator<br />

b downstream earthing switch 2 kA rms making capacity<br />

b operation counter on contactor<br />

b enlarged low-voltage control cabinet<br />

b mechanical interlocking between contactor and disconnector/earthing switch<br />

Version:<br />

b LPCT (only with Sepam series 20, series 40, series 80)<br />

25<br />

20<br />

16<br />

12.5<br />

Optional accessories:<br />

b cubicle:<br />

v auxiliary contacts on the disconnector<br />

v protection using Sepam programmable electronic unit<br />

v one to three voltage transformers<br />

v key-type interlocks<br />

v 50 W heating element<br />

v 1250 A three-phase upper busbars<br />

v 630 A three-phase upper busbars for severe operating conditions<br />

b contactor:<br />

v mechanical interlocking<br />

b equipment for three DIN striker fuses<br />

b mechanical indication system for blown fuses<br />

b auxiliary contact for blown fuses<br />

b DIN striker fuses<br />

Ur<br />

kV<br />