Modular units
Modular units
Modular units
You also want an ePaper? Increase the reach of your titles
YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.
DE58407<br />
Generalities Web Remote Monitoring<br />
SM6 Web Remote Monitoring<br />
with front face Intranet connector<br />
Functionalities provided<br />
Instantaneous readings<br />
Displays automatically updated meter values<br />
Circuit summary<br />
Displays the RMS current 3-phase average (A), the real power<br />
(kW), the power factor, the circuit breaker status (if applicable),<br />
etc.<br />
Load current summary<br />
Displays the current RMS value for each phase (A),<br />
for all circuits<br />
Demand current summary<br />
Displays the average demand current value for each phase (A),<br />
for all circuits<br />
Power summary<br />
Displays the present demand (kW), the peak demand (kW)<br />
and the times and dates of the records<br />
Energy summary<br />
Displays the energy (kWh) the reactive energy (kvarh),<br />
and the times and dates of the records<br />
Instantaneous readings, all devices<br />
Basic historical data logging, energy and trending<br />
Displays automatically updated meter values for all<br />
the communicating devices in the equipment<br />
Log displays<br />
Displays data as time curves, or tables<br />
Export of data tables<br />
Allows data tables to be exported in a standard Windows format<br />
DE59215EN<br />
Description<br />
b The EGX300 is an Ethernet-based device providing a simple transparent interface<br />
between Ethernet-based networks and fi eld devices as protective relays (Sepam).<br />
b The EGX300 has the ability to be used as a simple web based monitoring solution<br />
providing real-time data views, on-board data logging/trending, and simple control<br />
for fi eld devices.<br />
b The DM range of circuit breakers cubicles with Sepam ranges and one EGX300<br />
per switchboard for remote monitoring via the Intranet<br />
b An RJ45 Ethernet connector on the front of the switchboard, directly accessible<br />
from the front panel (option).<br />
For other SM6 confi gurations (with other devices or other Sepam product ranges), it<br />
is possible to integrate Web Remote Monitoring capability, consult your local<br />
Schneider Electric correspondent.<br />
Range selection<br />
This chart presents the different SM6 24 kV cubicles proposed with an industrialised<br />
Web Remote Monitoring system.<br />
Description Type of <strong>units</strong><br />
Single-isolation circuit breaker unit DM1-A, DMVL-A<br />
Single-isolation circuit breaker unit, right or left outgoing line DM1-D<br />
Withdrawable single-isolation circuit breaker unit DM1-W<br />
Withdrawable single-isolation circuit breaker unit, right outgoing line DM1-Z<br />
Double-isolation circuit breaker unit, right or left outgoing line DM2<br />
Typical design<br />
You need to have a Web server in only one CB unit to monitor the whole switchboard.<br />
Intranet, Ethernet TCP/IP<br />
Sepam<br />
EGX300<br />
PSU 24 Vdc<br />
Modbus serial link (1)<br />
EGX300<br />
42 AMTED398078EN.indd<br />
Sepam<br />
(1) Same cable CCR301 for RS 485 and PSU 24 V DC<br />
Sepam<br />
Sepam