DE58407<br />

Generalities Web Remote Monitoring<br />

SM6 Web Remote Monitoring<br />

with front face Intranet connector<br />

Functionalities provided<br />

Instantaneous readings<br />

Displays automatically updated meter values<br />

Circuit summary<br />

Displays the RMS current 3-phase average (A), the real power<br />

(kW), the power factor, the circuit breaker status (if applicable),<br />

etc.<br />

Load current summary<br />

Displays the current RMS value for each phase (A),<br />

for all circuits<br />

Demand current summary<br />

Displays the average demand current value for each phase (A),<br />

for all circuits<br />

Power summary<br />

Displays the present demand (kW), the peak demand (kW)<br />

and the times and dates of the records<br />

Energy summary<br />

Displays the energy (kWh) the reactive energy (kvarh),<br />

and the times and dates of the records<br />

Instantaneous readings, all devices<br />

Basic historical data logging, energy and trending<br />

Displays automatically updated meter values for all<br />

the communicating devices in the equipment<br />

Log displays<br />

Displays data as time curves, or tables<br />

Export of data tables<br />

Allows data tables to be exported in a standard Windows format<br />

DE59215EN<br />

Description<br />

b The EGX300 is an Ethernet-based device providing a simple transparent interface<br />

between Ethernet-based networks and fi eld devices as protective relays (Sepam).<br />

b The EGX300 has the ability to be used as a simple web based monitoring solution<br />

providing real-time data views, on-board data logging/trending, and simple control<br />

for fi eld devices.<br />

b The DM range of circuit breakers cubicles with Sepam ranges and one EGX300<br />

per switchboard for remote monitoring via the Intranet<br />

b An RJ45 Ethernet connector on the front of the switchboard, directly accessible<br />

from the front panel (option).<br />

For other SM6 confi gurations (with other devices or other Sepam product ranges), it<br />

is possible to integrate Web Remote Monitoring capability, consult your local<br />

Schneider Electric correspondent.<br />

Range selection<br />

This chart presents the different SM6 24 kV cubicles proposed with an industrialised<br />

Web Remote Monitoring system.<br />

Description Type of <strong>units</strong><br />

Single-isolation circuit breaker unit DM1-A, DMVL-A<br />

Single-isolation circuit breaker unit, right or left outgoing line DM1-D<br />

Withdrawable single-isolation circuit breaker unit DM1-W<br />

Withdrawable single-isolation circuit breaker unit, right outgoing line DM1-Z<br />

Double-isolation circuit breaker unit, right or left outgoing line DM2<br />

Typical design<br />

You need to have a Web server in only one CB unit to monitor the whole switchboard.<br />

Intranet, Ethernet TCP/IP<br />

Sepam<br />

EGX300<br />

PSU 24 Vdc<br />

Modbus serial link (1)<br />

EGX300<br />

42 AMTED398078EN.indd<br />

Sepam<br />

(1) Same cable CCR301 for RS 485 and PSU 24 V DC<br />

Sepam<br />

Sepam