31.12.2012 Views

Modular units

Modular units

Modular units

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

PE56822<br />

DE58404<br />

PE57169<br />

Generalities Ammeter<br />

b At the leading edge of technology,<br />

Amp 21D is suitable for Medium Voltage<br />

network load management.<br />

b Self-powered, it ensures a permanent<br />

display of currents.<br />

b Compact and in DIN format, it fi ts<br />

naturally into MV cubicles.<br />

b Cost effi cient, it uses the CT optimised<br />

for Fault Passage Indicator.<br />

b Performant, it displays phase current<br />

and maximum of current.<br />

Amp 21D<br />

AMTED398078EN.indd<br />

L1<br />

L2<br />

L3<br />

The SM6 integrates ammeter Amp 21D on all<br />

incoming cubicles and the fuse-switch cubicles<br />

Functions<br />

b Display of 3 phase current: I1 , I2 , I3. Range: 3 A to 800 A<br />

b Display of 3 phase current maximeter: I1 , I2 , I3. Range: 3 to 800 A.<br />

Display principle<br />

b Load curents are permanently displayed<br />

v continuous scrolling of L1, then L2, then L3.<br />

b Maximeter<br />

v access to maximeter display by pressing a dedicated push button<br />

v continuous scrolling of M1, then M2, then M3<br />

v reset of all maximeter by pressing a combination of two push buttons.<br />

Assembly<br />

Small size enclosure<br />

b DIN format : 93 x 45 mm<br />

b Secured, extraction-proof mounting<br />

b Terminal connections.<br />

Technical data<br />

Application<br />

Frequency 50 Hz and 60 Hz<br />

Load current<br />

Measurement<br />

Minimum current > 3 A<br />

Range Phase current 3 to 800 A<br />

Accuracy (I < 630 A) ± 5%, ± 2 A<br />

Reset of maximeter<br />

Power supply<br />

Manual from device Yes<br />

Self power From the current sensors I load > 3 A<br />

Battery No<br />

Auxiliary supply<br />

Display<br />

No<br />

Display 4 digits LCD<br />

Current per phase Yes (resolution 1 A)<br />

Sensors<br />

Maximeter per phase Yes<br />

Miscellaneous<br />

Phase CTs 3 split core CT<br />

Test Yes<br />

Characteristics<br />

Dielectric IEC 60255-5<br />

Electromagnetic IEC 61000-4-4 (level 4)<br />

IEC 61000-4-12<br />

Climatic Operating temperature<br />

Storage temperature<br />

Salt fog<br />

Mechanical IEC 60068-2-6<br />

IEC 60068-2-29<br />

Insulation 10 kV<br />

Shock wave 20 kV<br />

– 25°C to + 70°C<br />

– 40°C to + 85°C<br />

200 h<br />

Vibrations 10 to 500 Hz: 2 g<br />

Protection IP23<br />