PE57163<br />

61035N<br />

Characteristics of<br />

the functional <strong>units</strong><br />

Operating mechanisms<br />

Single-function operating mechanism<br />

for the SF circuit breakers 24 kV and 36 kV<br />

and Evolis 24 kV lateral<br />

b Circuit-breaker function<br />

v independent-operation closing in two steps.<br />

First operating mechanism recharge by motor or lever, then release of the stored<br />

energy by push-button (I) or trip unit.<br />

v independent-operation opening by push-button (O) or trip <strong>units</strong>.<br />

b Auxiliary contacts<br />

v circuit breaker (4 O + 4 C),<br />

v mechanism charged (1 C).<br />

b Mechanical indications<br />

Operation counter.<br />

b Opening releases<br />

v Mitop (low energy),<br />

v shunt trip,<br />

v undervoltage.<br />

b Closing release<br />

v shunt trip<br />

b Motor option (option and installation at a later date possible).<br />

Possible combinations between opening releases<br />

SF1 SFset<br />

Release type Combinations Combinations<br />

1 2 3 4 5 6 1 2 3 4<br />

Mitop (low energy) b b b b b b<br />

Shunt trip b b b b<br />

Undervoltage b b b b<br />

P2 stored energy operating mechanism<br />

for the Evolis circuit breaker 17.5 kV frontal<br />

b Circuit-breaker function<br />

v independent-switching operating closing in two steps.<br />

First operating mechanism recharge by motor or lever, then release of the stored<br />

energy by push-button (I) or trip unit.<br />

v independent-operation opening by push-button (O) or trip <strong>units</strong>.<br />

v spring energy release.<br />

b Auxiliary contacts<br />

v circuit breaker (4 O + 4 C),<br />

v mechanism charged (1 C).<br />

b Mechanical indications<br />

Operation counter.<br />

b Opening releases<br />

v Mitop (low energy),<br />

v shunt trip,<br />

v undervoltage.<br />

b Closing release<br />

v shunt trip<br />

b Motor option (option and installation at a later date possible).<br />