the functional <strong>units</strong><br />

Current transformer ARM6T<br />

AMTED398078EN.indd<br />

Current transformers for 36 kV<br />

For <strong>units</strong> DM1-A, DM1-D, DM1-W, DM2, DM2-W, IMC, GBC-A,<br />

GBC-B<br />

Transformer ARM6T/N1 or N2<br />

b double primary<br />

b double secondary winding for measurement and protection.<br />

Short-time withstand current Ith (kA)<br />

I1n (A) 50-100 75-150 100-200 150-300 200-400 300/600 1000/1250<br />

Ith (kA) 16 - 20 25<br />

t (s) 1 1<br />

Measurement 5 A 7.5 VA - 15 VA - class 0.5 30 VA<br />

and protection<br />

- class 0.5<br />

5 A 2.5 VA - 5 VA - 5P20 10 VA<br />

- 5P20<br />

Low Power Current Transformer (LPCT)<br />

For <strong>units</strong> DM1-A, DM1-W<br />

Transformer TLP 130, TLP 190<br />

b characteristics according to IEC standard 60044-8<br />

b large primary current range<br />

b direct output voltage for measurement and protection<br />

b RJ45-8 pts secondary connector<br />

b insulation level 0.72 kV<br />

b internal diameter 130 or 190 mm<br />

b in SM6-36, TLP 130 can be used for 630 A, TLP 190 can be used up to 1250 A.<br />

TLP 130 TLP 190<br />

Minimum rated primary current 5 A 5 A<br />

Rated extended primary current 1250 A 2500 A<br />

Secondary output 22.5 mV @ 100 A 22.5 mV @ 100 A<br />

Accuracy class for measurement 0.5 0.5<br />

Accuracy class for protection 5P 5P<br />

Accuracy limit factor 250 400<br />

Rated short time thermal current 25 kA 1 s 40 kA 1 s<br />

Highest voltage (Um) 0.72 kV 0.72 kV<br />

Rated power-frequency withstand 3 kV 3 kV<br />