Page 34<br />

➄ Terminating<br />

Resistor<br />

➀<br />

Shielded<br />

Twisted<br />

Pair<br />

DS<strong>II</strong><br />

Circuit<br />

<strong>Breaker</strong><br />

with<br />

OPTIM<br />

➆<br />

PONI <strong>Module</strong><br />

(Required for IMPACC<br />

Network Communications)<br />

Series C<br />

K-Frame<br />

MCCB<br />

with<br />

OPTIM<br />

Shielded<br />

Twisted<br />

Pair<br />

➁<br />

➃<br />

➁<br />

Series C<br />

L-Frame<br />

MCCB<br />

with<br />

OPTIM<br />

IBM Compatible<br />

Computer<br />

PONI<br />

<strong>Breaker</strong><br />

<strong>Interface</strong><br />

<strong>Module</strong><br />

➀ ➂<br />

SPB<br />

Circuit<br />

<strong>Breaker</strong><br />

with<br />

OPTIM<br />

Circuit<br />

<strong>Breaker</strong><br />

with<br />

RMS 810<br />

or 910<br />

➄ Terminating<br />

Resistor<br />

Figure 5-3 Typical Network Wiring Diagram<br />

➅<br />

➁<br />

➃<br />

Series C<br />

N-Frame<br />

MCCB<br />

with<br />

OPTIM<br />

Series C<br />

R-Frame<br />

MCCB<br />

with<br />

OPTIM<br />

➁ ➁<br />

Series C<br />

F-Frame<br />

MCCB<br />

ES<br />

Shielded<br />

Twisted<br />

Pair<br />

IQ Energy Sentinel<br />

➀<br />

I.B. 29C893B<br />

➀ For network interconnection cable,<br />

use Belden 9463 or Cutler-Hammer<br />

IMPCABLE.<br />

➁ When interconnecting devices, tie<br />

shield drain wires together for shield<br />

path continuity.<br />

➂ Connect the shield path to a solid<br />

earth ground at one point only.<br />

➃ On last device in network, tape shield<br />

drain wire back upon cable.<br />

➄ Use a 1/2 watt carbon or metal film<br />

resistor at each end of the network<br />

as an end of line termination resistor<br />

(EOLTR). EOLTR should be 100 ohms<br />

for 9600 baud communication rate<br />

networks or 150 ohms for 1200 baud<br />

communication rate networks.<br />

➅ Network interconnection to computer<br />

requires use of an IMPACC master<br />

(CONI or MINT).<br />

➆ Devices without built-in communications<br />

require network interface module<br />

(PONI).<br />

For detailed network wiring specifications,<br />

call the automatic fax retrieval system<br />

(FRED) at 412/494-3745 and request<br />

document 17513 or contact the<br />

Advanced Products Support Center.<br />

Refer to the paragraph entitled<br />

“Technical Assistance” in this document.<br />