9.14.5. Checking bit's value in the registry<br />

In case of <strong>MT</strong>-101-to-<strong>MT</strong>-101 communication (the cascade system), it is necessary to test<br />

values of receiving module's registers holding the status received last via GPRS from sending<br />

module. <strong>MT</strong>Prog recognizes it as: R<strong>MT</strong>_IN (input space), R<strong>MT</strong>_ID_OUT (sender's ID + output<br />

space), R<strong>MT</strong>_AN1 and R<strong>MT</strong>_AN2 (input AN1 respectively AN2).<br />

Scheme:<br />

Create the rule sending status<br />

triggered by any change of I1<br />

addressed to remote module<br />

Download the program that checks<br />

R<strong>MT</strong>_IN and the value of bit 9<br />

(corresponding to senders I1 input value)<br />

and sets Q1 accordingly.<br />

As the result, the value of binary input I1 at sending module will be mirrored by receiving<br />

module's binary output Q1.<br />

Line 0 copies the bit 9 of R<strong>MT</strong>_IN into REG1. Line 1 compares REG1 to 256<br />

(value of bit 9) and sets Q1 accordingly to the actual value.<br />

109