8.2.5.7.2. Number of retries<br />
Function - defines number of attempts to transmit data via PORT2 in case of<br />
unconfirmed (within time defined by transmission Timeout<br />
parameter) reception.<br />
Data type - number<br />
Range - 0…7<br />
Default value - 1<br />
Comments - value 0 results in sending without confirming faultless reception.<br />
8.2.5.7.3. Transmission timeout<br />
Function - Defines (in seconds) waiting time for confirmation of data frame<br />
reception.<br />
Data type - number<br />
Range - 0…10 [s]<br />
Default value - 2 [s]<br />
Comments - This value along with declared Number of retries influences max.<br />
time of single data packet transmission.<br />
8.2.5.7.4. Threshold hysteresis<br />
Function - Defines hysteresis for alarm thresholds values<br />
Data type - number<br />
Range - 0,01…100,00 [%]<br />
Default value - 5,00 [%]<br />
Comments - setting of value of hysteresis adequate to signal variations<br />
prevents untimely activations of alarm flags.<br />
8.2.5.7.5. Gas meter address<br />
Function - Defines address of gas meter connected to module's PORT 1<br />
Data type - number<br />
Range - 0…65535<br />
Default value - 0<br />
Comments - n/a<br />
8.2.5.7.6. Gas meter reading interval<br />
Function - Defines (seconds) interval of readings from peripheral device using<br />
GazModem protocol for update measurement data. The connection<br />
is via PORT 1<br />
Data type - number<br />
Range - 0…65535 [s]<br />
Default value - 180 [s]<br />
Comments - value 0 (zero) forces max. possible frequency of updating. It<br />
depends on speed of PORT2 along with size and number of defined<br />
mapped spaces.<br />
57