Comments - This parameter helps set an exclusive transmission channel to a<br />

remote device for a period of time. This enables establishing a<br />

system consisting of several devices with functionality similar to<br />

point-to-point.<br />

When a channel is established, the module ignores packets<br />

received from other devices and all data received at PORT 2 are<br />

sent to the module with which the channel is established.<br />

Transmission costs are thus reduced significantly. Packets are sent<br />

to all recipients only at first transmission.<br />

The function is activated by setting the value to other than zero<br />

thus defining the time channel is reserved. Time count starts from<br />

receiving first GPRS packet.<br />

Consecutive packets from same source prolong reservation time<br />

while sent packets do not.<br />

Setting this variable to 0 switches reservation off and module<br />

operates in standard way sending and receiving packets to all<br />

defined recipients.<br />

The function of channel reservation is independent on module<br />

access frames. Reception of such frame does not reserve the<br />

channel. Access to module from other master is possible when<br />

channel is reserved.<br />

8.2.5.6. GazModem mode<br />

CAUTION!<br />

Option discontinued from v 1.43 of firmware for module <strong>MT</strong>-<strong>102</strong>.<br />

The description is solely for legacy support.<br />

<strong>MT</strong>-<strong>102</strong> <strong>Module</strong> operating in GazModem mode enables communication with gas counters<br />

operating on GazModem transmission protocol. Data received at PORT2 are placed in<br />

respective registers of <strong>MT</strong>-<strong>102</strong> module's memory map.<br />

8.2.5.6.1. Read interval<br />

Function - Defines (in seconds) an interval between readings from peripheral<br />

device operating on GazModem protocol in order to update<br />

measurement data.<br />

Data type - number<br />

Range - 0…65535 [s]<br />

Default value - 180 [s]<br />

Comments - value 0 (zero) forces max. possible frequency of updating. It<br />

depends on speed of PORT2 along with size and number of defined<br />

mapped spaces.<br />

8.2.5.6.2. Number of retries<br />

Function - defines number of attempts to transmit data via PORT2 in case of<br />

unconfirmed (within time defined by transmission Timeout<br />

parameter) reception.<br />

Data type - number<br />

Range - 0…7<br />

Default value - 2<br />