Binary outputs space<br />

Alarm bits informing on comparison results with current values of gas counters.<br />

Star Address<br />

hex dec MODBUS<br />

Name Description<br />

0x0B8 184 10185 MC1V1LL LL alarm bit for VAR1, counter 1<br />

0x0B9 185 10186 MC1V1L L alarm bit for VAR1, counter 1<br />

0x0BA 186 10187 MC1V1H H alarm bit for VAR1, counter 1<br />

0x0BB 187 10188 MC1V1HH HH alarm bit for VAR1, counter 1<br />

0x0BC 188 10189 MC1V2LL LL alarm bit for VAR2, counter 1<br />

0x0BD 189 10190 MC1V2L L alarm bit for VAR2, counter 1<br />

0x0BE 190 10191 MC1V2H H alarm bit for VAR2, counter 1<br />

0x0BF 191 10192 MC1V2HH HH alarm bit for VAR2, counter 1<br />

0x0C0 192 10193 MC1V3LL LL alarm bit for VAR3, counter 1<br />

… … … … …<br />

0x0D7 215 <strong>102</strong>16 MC1V8HH HH alarm bit for VAR8, counter 1<br />

0x0D8 216 <strong>102</strong>17 MC2V1LL LL alarm bit for VAR1, counter 2<br />

… … … … …<br />

0x0F7 247 <strong>102</strong>48 MC2V8HH HH alarm bit for VAR8, counter 2<br />

0x0F8 248 <strong>102</strong>49 MC3V1LL LL alarm bit for VAR1, counter 2<br />

… … … … …<br />

0x2B7 695 10696 MC16V8HH HH alarm bit for VAR8, counter 16<br />

Bits informing on state of communication with gas meter<br />

Start Address<br />

hex dec MODBUS<br />

Name<br />

Description<br />

0A8 168 10169 SL1_ok 1 – proper communication with counter 1<br />

0A9 169 10170 SL2_ok 1 – proper communication with counter 2<br />

0AA 170 10171 SL3_ok 1 – proper communication with counter 3<br />

0AB 171 10172 SL4_ok 1 – proper communication with counter 4<br />

0AC 172 10173 SL5_ok 1 – proper communication with counter 5<br />

0AD 173 10174 SL6_ok 1 – proper communication with counter 6<br />

0AE 174 10175 SL7_ok 1 – proper communication with counter 7<br />

0AF 175 10176 SL8_ok 1 – proper communication with counter 8<br />

0B0 176 10177 SL9_ok 1 – proper communication with counter 9<br />

0B1 177 10178 SL10_ok 1 – proper communication with counter 10<br />

0B2 178 10179 SL11_ok 1 – proper communication with counter 11<br />

0B3 179 10180 SL12_ok 1 – proper communication with counter 12<br />

0B4 180 10181 SL13_ok 1 – proper communication with counter 13<br />

0B5 181 10182 SL14_ok 1 – proper communication with counter 14<br />

0B6 182 10183 SL15_ok 1 – proper communication with counter 15<br />

0B7 183 10184 SL16_ok 1 – proper communication with counter 16<br />