11.3. Power supply<br />
Direct Current DC (12V, 24V)<br />
Alternating current AC (24V)<br />
Input current (A) (for 12V DC)<br />
Input current (A) (for 24V DC)<br />
10.8 ... 36V<br />
18...26.4Vrms<br />
Idle 0.10<br />
Active 0.60<br />
Max 1.90<br />
Idle 0.06<br />
Active 0.25<br />
Max 1.00<br />
CAUTION!<br />
Due to high momentary current consumption the power supply must be<br />
capable of delivering >= 2A of current.<br />
Inappropriate power supply may result in faulty operation or cause damage<br />
to <strong>MT</strong>-<strong>102</strong> module!<br />
11.4. Binary outputs Q1...Q8<br />
Operating as binary output<br />
Recommended mean current for single<br />
output<br />
Single output current<br />
Mean current for all outputs<br />
Voltage drop for 350mA<br />
OFF state current<br />
50mA<br />
350mA max.<br />
400mA max.<br />
< 3.5V max.<br />
< 0.2mA max.<br />
Operating as binary input/counter<br />
Input voltage range<br />
Input resistance<br />
Input voltage ON (1)<br />
Input voltage OFF (0)<br />
Frequency range in analogue mode<br />
Min pulse length "1"<br />
0 ... 36V<br />
5.4 k<br />
> 9V<br />
< 3V max<br />
0 ... 2kHz<br />
5ms<br />
11.5. Analogue inputs AN1...AN6<br />
Analogue inputs AN1, AN2:<br />
Measuring range<br />
Max input current<br />
Dynamic input impedance<br />
Voltage drop for 20mA<br />
A/D converter<br />
Accuracy<br />
Non linearity<br />
4 ... 20 mA<br />
50 mA max.<br />
25 typ.<br />
< 5V max.<br />
10 bites<br />
1.5% max.<br />
1% max.<br />