Comments - value 0 (zero) forces max. possible frequency of updating. It<br />
depends on speed of PORT2 along with size and number of defined<br />
mapped spaces.<br />
8.2.5.6.3. Transmission timeout<br />
Function - Defines (in seconds) waiting time for confirmation of data frame<br />
reception.<br />
Data type - number<br />
Range - 0…10 [s]<br />
Default value - 2 [s]<br />
Comments - This value along with declared Number of retries influences max.<br />
time of single data packet transmission.<br />
8.2.5.6.4. Threshold hysteresis<br />
Function - Defines hysteresis for alarm thresholds values<br />
Data type - number<br />
Range - 0,01…100,00 [%]<br />
Default value - 2,00 [%]<br />
Comments - setting of value of hysteresis adequate to signal variations<br />
prevents untimely activations of alarm flags.<br />
8.2.5.6.5. Alarm station IP address<br />
Function - defines alarm recipient's IP address.<br />
Data type - selection list<br />
List<br />
- friendly names assigned to IP addresses of devices declared in<br />
Authorized numbers list<br />
Default value - IP1 - first number on authorized numbers list<br />
Comments - since recipient's IP address is selected from selection list, it is<br />
practical to define unique unambiguous names facilitating<br />
identification on the list.<br />
8.2.5.6.6. Number of devices<br />
Function - Defines number of declared register spaces (devices) read on<br />
PORT2 from peripheral devices operating on GazModem protocol<br />
Data type - number<br />
Range - 1…16<br />
Default value - 1<br />
Comments - n/a<br />
54