FLUE OUTLET<br />
20<br />
17 FLUE EXTENSION DUCTS - continued<br />
1. A maximum of 6 extension ducts for the HE24/<br />
HE30 and a maximum of 3 extension ducts for<br />
the HE35 (one suitably cut) plus the standard<br />
flue duct may be used together.<br />
2. Flue extensions of greater length than 1m (39")<br />
should be supported with the bracket provided,<br />
suitably adjusted. Refer to Frames 16 and 24.<br />
3. Only use water as a lubricant during assembly.<br />
Do not use mineral based oils.<br />
18 FITTING THE KIT<br />
INSTALLATION<br />
16 FLUE EXTENSION DUCTS - For total flue lengths greater than 595mm<br />
Pack D Flue extension duct kit contents<br />
Extension duct & clamp<br />
1.0m (39") long<br />
nm8732<br />
General arrangement<br />
Flue duct support<br />
Use a maximum of 6m extended flue ONLY (HE24 & 30)<br />
Use a maximum of 3m extended flue ONLY (HE35)<br />
Because of the flexibility of the telescopic flue terminal it is not<br />
always necessary to cut an extension pack.<br />
1. Measure the total flue length from the centre of the boiler<br />
outlet to the outside wall.<br />
2. Subtract 70mm from this dimension.<br />
3. Subtract 950mm for each ‘D’ pack to be used.<br />
4. If the remainder Y is 300mm -<br />
525mm this can be taken up 70<br />
by the adjustment in the<br />
telescopic flue.<br />
5. If the remainder Y is 525mm -<br />
950mm it will be necessary to<br />
cut a ‘D’ pack to 400mm.<br />
esp8940<br />
950<br />
Flue support cutting aid<br />
(shown folded up)<br />
Wall plugs - 4 off<br />
No. 10 x2" wood screw - 4 off<br />
Boiler<br />
nm8762<br />
Flue length<br />
Extension flue<br />
Standard flue<br />
Terminal grille<br />
Note. Side flue shown<br />
6. If the remainder Y is less than 300mm, shorten the<br />
previous ‘D’ pack to 400mm and adjust the telescopic<br />
terminal.<br />
7. Measure and mark the length on the flue, to ensure a<br />
square cut mark the flue all the way around and cut to<br />
length.<br />
L<br />
Y<br />
525<br />
300<br />
Esprit - Installation and Servicing