87 L.....A..... (OVERHEAT ERROR)<br />

Can the overheat condition be reset by pressing<br />

the boiler reset button when the system is cold ?<br />

Does the pump setting give a differential<br />

across the boiler in excess of 25 o C ?<br />

Set CH control knob to maximum.<br />

If the overheat trips again measure the flow temp:<br />

Over 90 o C Check control thermistor<br />

(Refer to Frame 90)<br />

Under 90 o C Replace overheat 'stat<br />

Esprit - Installation and Servicing<br />

YES<br />

Is the boiler and CH system filled with<br />

water and all isolation valves open ?<br />

YES (also refer to Frame 88)<br />

NO<br />

FAULT FINDING<br />

NO<br />

YES<br />

88 L.....E..... OR L.....A..... (WATER PRESSURE SWITCH)<br />

Note.<br />

LE occurs when boiler is cold.<br />

LA occurs when boiler is hot.<br />

Can the overheat condition be reset by pressing<br />

the boiler reset button when the system is cold ?<br />

89 L....8..... (FAN ERROR)<br />

Is nominal 330 V DC present across<br />

red and blue at the fan connector as<br />

reset button is pressed?<br />

NO<br />

NO<br />

Is the boiler and CH system filled with water<br />

with a minimum pressure of 1.0 bar (cold)<br />

and all isolation valves open?<br />

YES (also refer to Frame 86)<br />

Is 230V available across the water pressure<br />

switch electrical leads<br />

YES<br />

Replace water pressure switch<br />

NO<br />

YES Is 14V DC present across<br />

yellow and pink at the fan<br />

connector?<br />

NO<br />

Check wiring harness for continuity.<br />

Is there continuity?<br />

Replace overheat thermostat<br />

Fill and vent the system and open all<br />

isolation valves<br />

Check that the pump is rotating freely.<br />

Is differential now below 25 o C ?<br />

Replace the system pump<br />

YES<br />

NO<br />

YES<br />

NO YES<br />

Note. With V9 Primary Control PCB, overheat LA/HA or H9/L9 when<br />

reset will display 3 horizontal lines and will not attempt to refire until<br />

the temperature in the heat exchanger drops below 50 o C.<br />

YES<br />

NO<br />

NO<br />

OK<br />

Replace PCB<br />

OK<br />

Fill and vent the system and open all<br />

isolation valves<br />

Note. With V9 Primary Control PCB, overheat LA/HA or H9/L9 when<br />

reset will display 3 horizontal lines and will not attempt to refire until<br />

the temperature in the heat exchanger drops below 50 o C.<br />

Replace fan<br />

Replace PCB<br />

Replace harness<br />

61<br />

FAULT FINDING FAULT FINDING FAULT FINDING FAULT FINDING FAULT FINDING