87 L.....A..... (OVERHEAT ERROR)<br />
Can the overheat condition be reset by pressing<br />
the boiler reset button when the system is cold ?<br />
Does the pump setting give a differential<br />
across the boiler in excess of 25 o C ?<br />
Set CH control knob to maximum.<br />
If the overheat trips again measure the flow temp:<br />
Over 90 o C Check control thermistor<br />
(Refer to Frame 90)<br />
Under 90 o C Replace overheat 'stat<br />
Esprit - Installation and Servicing<br />
YES<br />
Is the boiler and CH system filled with<br />
water and all isolation valves open ?<br />
YES (also refer to Frame 88)<br />
NO<br />
FAULT FINDING<br />
NO<br />
YES<br />
88 L.....E..... OR L.....A..... (WATER PRESSURE SWITCH)<br />
Note.<br />
LE occurs when boiler is cold.<br />
LA occurs when boiler is hot.<br />
Can the overheat condition be reset by pressing<br />
the boiler reset button when the system is cold ?<br />
89 L....8..... (FAN ERROR)<br />
Is nominal 330 V DC present across<br />
red and blue at the fan connector as<br />
reset button is pressed?<br />
NO<br />
NO<br />
Is the boiler and CH system filled with water<br />
with a minimum pressure of 1.0 bar (cold)<br />
and all isolation valves open?<br />
YES (also refer to Frame 86)<br />
Is 230V available across the water pressure<br />
switch electrical leads<br />
YES<br />
Replace water pressure switch<br />
NO<br />
YES Is 14V DC present across<br />
yellow and pink at the fan<br />
connector?<br />
NO<br />
Check wiring harness for continuity.<br />
Is there continuity?<br />
Replace overheat thermostat<br />
Fill and vent the system and open all<br />
isolation valves<br />
Check that the pump is rotating freely.<br />
Is differential now below 25 o C ?<br />
Replace the system pump<br />
YES<br />
NO<br />
YES<br />
NO YES<br />
Note. With V9 Primary Control PCB, overheat LA/HA or H9/L9 when<br />
reset will display 3 horizontal lines and will not attempt to refire until<br />
the temperature in the heat exchanger drops below 50 o C.<br />
YES<br />
NO<br />
NO<br />
OK<br />
Replace PCB<br />
OK<br />
Fill and vent the system and open all<br />
isolation valves<br />
Note. With V9 Primary Control PCB, overheat LA/HA or H9/L9 when<br />
reset will display 3 horizontal lines and will not attempt to refire until<br />
the temperature in the heat exchanger drops below 50 o C.<br />
Replace fan<br />
Replace PCB<br />
Replace harness<br />