ARTICLE 303<br />
Installations for customer convenience will be installed at the<br />
customer’s expense. In any event, prior to ordering equipment<br />
or starting a wiring installation involving both single phase and<br />
three phase operation, the NSTAR New Customer Connect<br />
Tech Center must be contacted regarding the characteristics of<br />
the service to be supplied.Where electricity is delivered<br />
through more than one meter, the cost of energy delivered<br />
through each meter will be computed separately.<br />
303. Service Characteristics<br />
The following describes the characteristics and nominal<br />
voltages of standard services, which are generally available.To<br />
determine the type of service available at your location, please<br />
contact the NSTAR New Customer Connect Tech Center. All<br />
secondary voltage values stated herein are nominal, and are<br />
subject to reasonable variations in accordance with the latest<br />
revision of ANSI C84.<br />
34<br />
NOTE:<br />
The Downtown Boston Network District as<br />
mentioned in this book is defined as Boston proper, Back<br />
Bay, portions of the South End and the Fenway. (See map at<br />
front of book.)<br />
For the North districts -formally Boston Edison<br />
A. 120/240 volts, single phase, 3 wire, service & 240<br />
volts, three phase, 3 wire, Delta service<br />
Generally available outside the Downtown Boston<br />
Network District. Single phase motors are limited to 5<br />
horsepower or less.Three phase service is required for<br />
motors exceeding 5 HP in size.The maximum combined<br />
single-and three phase load to be served from NSTAR<br />
facilities in the public way is limited to 150 kVa where<br />
available. Customers requiring service beyond this limit<br />
ARTICLE 303<br />
must provide suitable private property facilities for necessary<br />
transformation as coordinated by the NSTAR New<br />
Customer Connect Tech Center.<br />
B. 480 volts, three phase, 3 wire, Delta service<br />
Generally available where the customer provides suitable<br />
private property facilities for necessary transformation.<br />
C. 120/280 volts, single phase, 3 wire, service<br />
Normally available only in the Downtown Boston Network<br />
District for connected loads not greater than 200 amperes.<br />
This service may be available upon consultation with<br />
NSTAR. Larger services must be three phase, 4 wire.<br />
D. 120/208 volts, 3 phase, 4 wire,Wye service<br />
Within the Downtown Boston Network District, some<br />
locations requiring loads up to 300 kVa (800 amperes) of<br />
transformer capacity may be supplied from NSTAR facilities<br />
in the public way. In locations where transformer capacity in<br />
the public way is not readily available, the customer will be<br />
required to provide suitable private property facilities for<br />
the supply transformers. For loads exceeding 300 kVa (800<br />
amperes), the customer must provide suitable private<br />
property facilities for the supply transformers as<br />
coordinated by the NSTAR New Customer Connect Tech<br />
Center.<br />
Outside the Downtown Boston Network District, the<br />
customer may be requested to provide suitable private<br />
property facilities for necessary transformation.<br />
E. 277/480 volts, three phase, 4 wire,Wye service<br />
Generally available except that the customer must provide<br />
suitable private property facilities for necessary<br />
transformation. Minimum demand loads are a requisite,<br />
typically 75 kVa or larger.<br />