01.01.2015 Views

INFORMATION & REQUIREMENTS ELECTRIC SERVICE - NStar

INFORMATION & REQUIREMENTS ELECTRIC SERVICE - NStar

INFORMATION & REQUIREMENTS ELECTRIC SERVICE - NStar

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

SKETCH 25<br />

Mounting Provisions and Dimensions For Metering Current Transformers<br />

In Service Cubicles Rated 600 Volts, 1800 Amperes or Less<br />

MIN. MIN. MIN. MIN.<br />

4 1"<br />

8 1" 8 1" 4 1"<br />

2 2 2 2<br />

CLEARANCE TO<br />

NEAREST OBJECT<br />

FIGURE 1 FIGURE 2<br />

BUS SPACING<br />

SIDE VIEW<br />

IN CUBICLE<br />

OF CUBICLE<br />

1 1"<br />

2<br />

1"<br />

1"<br />

5 7"<br />

8<br />

SEE FIG. 3 & 4<br />

7"MIN.<br />

7"MIN.<br />

1/4"-20 TAPPED HOLES<br />

ON LINE SIDE ONLY,<br />

AND ON NEUTRAL BUS<br />

11"<br />

2<br />

1 1"<br />

1"<br />

2<br />

1<br />

2<br />

ALL MOUNTING HOLES 9/16" DIA.<br />

ACCESS DOOR<br />

OF CUBICLE<br />

7"<br />

APPROX.<br />

MIN.<br />

7"<br />

8 1"<br />

2<br />

INSULATED BUS<br />

SUPPORTS<br />

1 3"<br />

4<br />

10"<br />

1 3"<br />

4<br />

ALL MOUNTING HOLES 9/16" DIA.<br />

FIGURE 3 FIGURE 4<br />

225A-1200A<br />

(1400A TO<br />

SWITCH OR C/B<br />

1800A SWITCH<br />

(WITH 1200A<br />

OR C/B)<br />

FRAME MAX.)<br />

7"<br />

8<br />

SKETCH 25 (NOTES)<br />

1. It is the responsibility of the customer to contact the Company for<br />

proper dimensions and mounting provisions for each set of metering<br />

current transformers.<br />

2. Current transformers are to be supplied and mounted by NSTAR<br />

on the bus, on the load side of the service circuit breaker or switch.<br />

3. Current transformers are to be mounted on the face of the bus<br />

toward the access door of the cubicle. If multiple busses are used,<br />

spacers will be furnished & installed by the manufacturer.<br />

4. No physical supports other than the primary terminals are required<br />

for the current transformers.<br />

5. The access door to the current transformer compartment must be<br />

hinged and have a locking hasp for a padlock type seal.<br />

6. Figure 1 shows a 4 wire-3Ø installation. On 3 wire – 3Ø & 3 wire –<br />

1Ø installations, transformers are to be mounted on outside busses<br />

only & filler bus for the common phase or neutral will be furnished &<br />

installed by the manufacturer.<br />

7. The manufacturer will furnish and install hex head machine bolts 1/2<br />

inch – 13 thread, nuts, washers for current transformer mounting,<br />

and 1/4 inch – 20 potential screws.<br />

8. The cubicle should be located in the switch room where there is a<br />

minimum clearance of 3 feet from the door of the cubicle to a wall<br />

or other obstruction.<br />

9. Meters are to be located on the outside of the building. A 1-1/2 inch<br />

conduit for the secondary wiring will be required from the current<br />

transformer location to the meter location. This conduit is not to<br />

exceed 25 feet unless written permission has been obtained. A pull<br />

string is required for wiring installation.<br />

10.Line side bus must be clearly identified.<br />

134<br />

135

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!