ARTICLE 715<br />

86<br />

3. Three phase, 3 wire delta, 240 and 480 volt service:<br />

A 5 terminal meter socket with manual bypass is<br />

required. (See Sketch 19)<br />

4. Three phase, 4 wire wye, 120/208 and 277/480 volt<br />

service: A 7 terminal meter socket with manual bypass<br />

is required. (See Sketch 20)<br />

C. 400 Amperes or Less (320 Amperes Continuous<br />

Load Capacity)<br />

In general, self-contained socket metering (class 320) is<br />

standard practice on single phase and three phase<br />

installations where the service capacity is greater than<br />

200 amperes and less than or equal to 400 amperes and the<br />

voltage is not greater than 480 volts.<br />

All class 320 meter installations shall be pre-approved by<br />

the local inspection authority prior to starting work.<br />

All approved class 320 meter sockets must be listed for use<br />

by a recognized testing agency and have a single lever type<br />

manually operated bypass, locking jaws, and safety shield.<br />

All 480 volt, 3 wire and 4 wire services shall be equipped<br />

with a disconnect switch ahead of each meter socket and<br />

shall be within sight of the meter socket (cold sequence). If<br />

the disconnect switch is not visible at the meter location<br />

then it must be a lockable device.<br />

The following is a list of socket meter requirements for<br />

class 320 meter sockets:<br />

1. Single phase, 3 wire, 120/240 or 120/208 volts:<br />

A 5 terminal (in the 6 o’clock position) meter socket<br />

with manual bypass is required. (See Sketch 21)<br />

2. Three phase, 4 wire wye, 120/208 or 277/480 volts:<br />

A 7 terminal meter socket with manual bypass is<br />

required. (See Sketch 22)<br />

ARTICLE 716-720<br />

D. Sockets for 200 Amperes or Less Residential or<br />

Commercial Underground Services<br />

All 200 amperes or less 120/240 or 120/208 voltage<br />

residential or commercial underground services shall be<br />

ringless type with lugs on the left side of the meter socket<br />

and bus bar connections to the line side of the meter jaws:<br />

Residential Milbank CAT#U1980-0 or equivalent cooper<br />

B-line CAT#EN20L44GRST or equivalent Siemans/Landis<br />

& Gyr CAT#SUAS877-PG or equivalent.<br />

Commercial-MILBANK CAT #U3924-XL or equivalent.<br />

Any conduit attaching to this meter socket should have<br />

expansion joints.<br />

716. Cover Plates<br />

In those instances where the meter cannot be immediately<br />

installed upon completion of the wiring in the meter socket,<br />

the customer is responsible to have a rigid plastic transparent<br />

cover with blades installed in the meter socket. This cover<br />

shall prevent accidental contact with any energized parts of the<br />

socket as well as providing physical protection until the meter<br />

can be installed. Under no circumstances shall cardboard be<br />

substituted for the above described cover.<br />

INSTRUMENT TRANSFORMER INSTALLATION<br />

720. Instrument Transformers and Enclosures<br />

It is the responsibility of the customer to contact the NSTAR<br />

New Customer Connect Tech Center or the NSTAR web site<br />

(www.nstar.com) for the proper dimensions and mounting<br />

provisions for each set of metering current transformers.<br />

The customer will furnish and install:<br />

A. Current transformer cabinet with the following:<br />

87