ARTICLE 715<br />
86<br />
3. Three phase, 3 wire delta, 240 and 480 volt service:<br />
A 5 terminal meter socket with manual bypass is<br />
required. (See Sketch 19)<br />
4. Three phase, 4 wire wye, 120/208 and 277/480 volt<br />
service: A 7 terminal meter socket with manual bypass<br />
is required. (See Sketch 20)<br />
C. 400 Amperes or Less (320 Amperes Continuous<br />
Load Capacity)<br />
In general, self-contained socket metering (class 320) is<br />
standard practice on single phase and three phase<br />
installations where the service capacity is greater than<br />
200 amperes and less than or equal to 400 amperes and the<br />
voltage is not greater than 480 volts.<br />
All class 320 meter installations shall be pre-approved by<br />
the local inspection authority prior to starting work.<br />
All approved class 320 meter sockets must be listed for use<br />
by a recognized testing agency and have a single lever type<br />
manually operated bypass, locking jaws, and safety shield.<br />
All 480 volt, 3 wire and 4 wire services shall be equipped<br />
with a disconnect switch ahead of each meter socket and<br />
shall be within sight of the meter socket (cold sequence). If<br />
the disconnect switch is not visible at the meter location<br />
then it must be a lockable device.<br />
The following is a list of socket meter requirements for<br />
class 320 meter sockets:<br />
1. Single phase, 3 wire, 120/240 or 120/208 volts:<br />
A 5 terminal (in the 6 o’clock position) meter socket<br />
with manual bypass is required. (See Sketch 21)<br />
2. Three phase, 4 wire wye, 120/208 or 277/480 volts:<br />
A 7 terminal meter socket with manual bypass is<br />
required. (See Sketch 22)<br />
ARTICLE 716-720<br />
D. Sockets for 200 Amperes or Less Residential or<br />
Commercial Underground Services<br />
All 200 amperes or less 120/240 or 120/208 voltage<br />
residential or commercial underground services shall be<br />
ringless type with lugs on the left side of the meter socket<br />
and bus bar connections to the line side of the meter jaws:<br />
Residential Milbank CAT#U1980-0 or equivalent cooper<br />
B-line CAT#EN20L44GRST or equivalent Siemans/Landis<br />
& Gyr CAT#SUAS877-PG or equivalent.<br />
Commercial-MILBANK CAT #U3924-XL or equivalent.<br />
Any conduit attaching to this meter socket should have<br />
expansion joints.<br />
716. Cover Plates<br />
In those instances where the meter cannot be immediately<br />
installed upon completion of the wiring in the meter socket,<br />
the customer is responsible to have a rigid plastic transparent<br />
cover with blades installed in the meter socket. This cover<br />
shall prevent accidental contact with any energized parts of the<br />
socket as well as providing physical protection until the meter<br />
can be installed. Under no circumstances shall cardboard be<br />
substituted for the above described cover.<br />
INSTRUMENT TRANSFORMER INSTALLATION<br />
720. Instrument Transformers and Enclosures<br />
It is the responsibility of the customer to contact the NSTAR<br />
New Customer Connect Tech Center or the NSTAR web site<br />
(www.nstar.com) for the proper dimensions and mounting<br />
provisions for each set of metering current transformers.<br />
The customer will furnish and install:<br />
A. Current transformer cabinet with the following:<br />
87