SKETCH 9<br />

SKETCH 10<br />

800-1000 Ampere Special Terminal Box<br />

Required Clearances Around NSTAR Owned Facilities<br />

NSTAR Facilities include:<br />

TERMINAL LUGS<br />

(SEE BELOW)<br />

ALL TERMINAL BOXES SHALL<br />

HAVE 1/4" DRAIN HOLES<br />

THROUGH BOTTOM OF<br />

TERMINAL BOX<br />

TERMINAL LUGS<br />

<strong>SERVICE</strong> ENTRANCE CABLES<br />

#14 GUAGE GALVANIZED STEEL (MIN)<br />

APPROVED NON-COMBUSTIBLE<br />

INSULATING SUPPORT,<br />

CENTER MOUNTED IN BOX<br />

FLAT BAR COPPER BUS CONDUCTOR OF<br />

PROPER CURRENT CAPACITY<br />

SPECIAL TERMINAL BOX TO<br />

BE SIZED PER THE MA <strong>ELECTRIC</strong>AL CODE<br />

WITH A MINIMUM SIZE OF 48"X48"X20"<br />

TO CUSTOMER<br />

1.Transformer/foundations,<br />

splice/junction boxes,<br />

manholes, switch gear/<br />

foundations and,<br />

handholes/pedestals.<br />

2. Shaded clearance area<br />

surrounding nstar<br />

facilities shall be clear of<br />

all plantings,<br />

uncontrolled growth,and<br />

the installation of<br />

unauthorized structures.<br />

This is to ensure that<br />

NSTAR will have the<br />

necessary clearance to<br />

operate and maintain<br />

their equipment.<br />

4 FEET MIN.<br />

(NOTE 3)<br />

EDGE OF ROAD<br />

4<br />

FEET<br />

2-4<br />

INCHES<br />

<strong>ELECTRIC</strong>AL<br />

FACILITY*<br />

(NOTE 1)<br />

EDGE OF PAVEMENT<br />

PLAN VIEW<br />

TELCO<br />

CATV<br />

LAYOUT<br />

SHADED AREA TO BE CLEAR OF ALL<br />

LANDSCAPING & ALL<br />

METERING EQUIPMENT<br />

SEE NOTE 2<br />

4<br />

FEET<br />

1"<br />

3" 1 1 /4"<br />

1 1 /2"<br />

3"<br />

CUSTOMER TO<br />

DRILL HOLES 7 /16" AND FURNISH 3 /8" -16 REQUIRED<br />

LENGTH BOLTS EACH WITH WASHER AND NUT.<br />

ALL SILICON BRONZE OR EQUIVALENT. THE COMPANY<br />

WILL CONNECT <strong>SERVICE</strong> ENTRANCE CABLES ONLY,<br />

USING CUSTOMER-SUPPLIED LUGS.<br />

3. Meter pedestals for<br />

temporary or permanent<br />

services shall not be<br />

installed within a<br />

minimum of 4 feet of a<br />

transformer pad.<br />

4. Handholes installed in<br />

paved surfaces shall be<br />

even, but not below,<br />

finished grade.<br />

4<br />

FEET<br />

1/2 IN.<br />

ELEVATION<br />

TYPICAL<br />

TRANSFORMER<br />

(NOTE 4)<br />

4<br />

FEET<br />

ELEVATION<br />

TYPICAL HANDHOLE<br />

118<br />

119