SKETCH 6B<br />

SKETCH 6B (NOTES)<br />

Typical Residential Underground Service from<br />

Overhead Facilities on Opposite Side of Street<br />

1. Local wiring authorities may have additional requirements to those<br />

shown here.<br />

10'<br />

NSTAR OR JOINTLY OWNED POLE<br />

CONTRACTOR SHALL LEAVE A 20' LONG<br />

(UNCUT)COIL OF CABLE FOR NSTAR TO<br />

LATER CONNECT TO OVERHEAD SUPPLY<br />

RISER PIPE AND CONDUIT TO<br />

HAND-HOLE SEE NOTES<br />

Meter by NSTAR<br />

U.G. <strong>SERVICE</strong> INSTALLED PER MASS. ELECT. CODE<br />

ONE LOOP OF CABLE IN HAND-HOLE<br />

OR USE SUBMERSIBLE-TYPE CONNECTOR<br />

6 FEET MAX<br />

3 FEET MIN<br />

2. If Customer’s cable from the hand-hole to the meter is direct buried,<br />

it should be slack in trench to allow for settling and frost. For<br />

roadway crossing section, unless there are stricter requirements by<br />

state or local ordinances, use minimum 3 inch diameter schedule 80<br />

PVC from the handhole to the riser backfilled with clean sand and<br />

red “<strong>ELECTRIC</strong>” marker tape above it.<br />

3. Riser pipe, sweep and conduit to hand-hole shall be minimum 3<br />

inches steel (R.M.C.) or schedule. 80 PVC conduit, R.M.C. requires<br />

a grounding connector for connection to #4 CU wire.<br />

POLE GROUND WIRE<br />

& CONNECTION BY NSTAR<br />

ELEVATION<br />

<strong>SERVICE</strong><br />

PANEL<br />

SEE NOTE 2<br />

4. Weather seal riser pipe opening around cables with duct sealing<br />

compound (UL R13335).<br />

5. The service conduit exiting the hand-hole towards the meter requires<br />

a watertight seal around the cables. As required by Massachusetts<br />

Electric Code. Use product like 3M Co. Scotchcast #2135.<br />

POLE<br />

MUNICIPAL<br />

PROPERTY<br />

STREET<br />

PRIVATE PROPERTY<br />

ALL WORK IN THE PUBLIC WAY WILL BE<br />

PERFORMED BY NSTAR<br />

CUSTOMER SHALL FURNISH AND INSTALL ENTIRE<br />

<strong>SERVICE</strong> EXCEPT FOR THE METER (BY NSTAR)<br />

ALTERNATE METER (PEDESTAL) LOCATION<br />

6. If an NSTAR representative requires an oversized riser cable section<br />

to accommodate potential future loading, NSTAR will supply those<br />

materials at no charge.<br />

CUSTOMER OWNS & MAINTAINS THIS PORTION<br />

NSTAR OWNS & MAINTAINS THIS PORTION, INCLUDING HAND-HOLE<br />

114<br />

115