INFORMATION & REQUIREMENTS ELECTRIC SERVICE - NStar
INFORMATION & REQUIREMENTS ELECTRIC SERVICE - NStar
INFORMATION & REQUIREMENTS ELECTRIC SERVICE - NStar
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
SKETCH 5<br />
SKETCH 5 (NOTES)<br />
Overhead Service Installation of Service Bolt<br />
FRAME<br />
BUILDING<br />
VENEER<br />
SIDING<br />
5/8" x 8" MACHINE BOLT<br />
5/8" x 12" MACHINE BOLT<br />
BOLT HEAD<br />
COUNTERSUNK<br />
AT LEAST<br />
3"<br />
2"<br />
BOLT HEAD<br />
COUNTERSUNK<br />
AT LEAST<br />
3"<br />
2"<br />
CHECK<br />
NUT<br />
CHECK<br />
NUT<br />
BLOCK FASTENED SECURELY<br />
TO STUDDING<br />
STUDDING<br />
BOARDING<br />
SHINGLES OR<br />
OTHER FINISH<br />
STANDARD NUT & WASHER<br />
SPOOL AND CLEVIS<br />
BLOCK FASTENED SECURELY<br />
TO STUDDING<br />
BOARDING<br />
STUDDING<br />
VENEER SIDING<br />
STANDARD NUT & WASHER<br />
SPOOL AND CLEVIS<br />
1. Bolts to be furnished and installed by customer in location to be<br />
specified by the company.<br />
2. Bolts & nuts to be hot dipped galvanized, to have machine thread & to<br />
project 2 inches beyond outer face of building, except where<br />
otherwise specified.<br />
3. Bolt may be put through studding or other suitable timber provided<br />
the location is correct for the service connection.<br />
4. Service attachment to be installed, not to cause service wire damage<br />
against structures and violate Massachusetts electrical safety<br />
codes/rules.<br />
TOP VIEW<br />
AT LEAST<br />
4"<br />
STUDDING<br />
LATHS<br />
WASHER<br />
BRICK<br />
BUILDING<br />
FURRING<br />
5/8" x 12"<br />
MACHINE BOLT<br />
STANDARD NUT & WASHER<br />
SPOOL AND CLEVIS<br />
THIS NUT TO BE SET UP TIGHT<br />
AGAINST WALL TO PREVENT BOLT<br />
BACKING UP OR TURNING<br />
2 1/2"<br />
AT LEAST<br />
3"<br />
110<br />