SKETCH 11<br />
Padmounted Transformer Protection From Vehicular Traffic<br />
SKETCH 12<br />
Temporary Service Structure for Service 200 Amperes or Less<br />
Service Structure 3' Min. in Ground<br />
Approved Weatherhead<br />
Service Drop Cable<br />
(Max. Span 100')<br />
4<br />
APPROX.<br />
4' TO TOP<br />
OF BRACE<br />
See<br />
Note 2<br />
4<br />
4<br />
Service Entrance<br />
Cable<br />
All Wood<br />
Braces 2"x4"<br />
Meter<br />
10' MIN<br />
NSTAR Electric shall:<br />
A. Make service drop<br />
cable connection to<br />
its distribution system<br />
1' Max.<br />
B. Furnish, install, and<br />
maintain the meter<br />
APPROX.<br />
5'<br />
Ground<br />
Conductor<br />
APPROX.<br />
5'<br />
Buried Ground<br />
Rod<br />
All Stakes<br />
(Wood)<br />
2"x4"x3'<br />
1. The above specified clear area distances to buildings or landscaping<br />
shall be maintained to: inspect, provide access, perform switching and<br />
ventilate the transformer.<br />
2. If no curb exists, or transformer is located closer than 10 feet to the<br />
traveled way, protective vehicle posts shall be installed on exposed side<br />
as specified.<br />
3. Vehicle posts shall be 4 inches galvanized steel pipe minimum, filled<br />
with concrete and extend 42 inches above and below grade. Larger<br />
diameter posts may be required for some installation.<br />
4. Contact NSTAR to ensure transformer meets the minimum distances<br />
to doors windows, fire escapes, air intakes and walls.<br />
120<br />
1. 6 inches X 6 inches timber shall extend into ground a minimum of<br />
3 feet.<br />
2. Service structures for road crossings must be of sufficient height to<br />
maintain an 18 feet minimum road clearance. If drop does not cross<br />
street, clearance may be reduced to 12 feet.<br />
3. All timbers to be sound and free of knots.<br />
4. Minimum of 4-10d nails or larger at each joint.<br />
5. Grounding conductor shall be stapled to timber at frequent intervals.<br />
6. Equivalent structure may be used with the approval of NSTAR.<br />
7. Approved manual bypass required.<br />
121