ARTICLE 428<br />

terminal box to provide for connection to NSTAR service<br />

conductors.Where the service entrance conductors are 350<br />

KCMIL or larger, the minimum length for each conductor shall<br />

be 3 feet.<br />

428. Terminal Facilities / Terminal Boxes<br />

Under all circumstances, terminal facilities shall be furnished,<br />

installed, owned and maintained by the customer. All terminal<br />

boxes shall be provided with a means for padlocking by<br />

NSTAR.The locking mechanism shall consist of two (2)<br />

locking hasps located on opposite sides of the terminal box. For<br />

services rated at 800-1000 amperes, see Sketch 9 for additional<br />

requirements. All terminal boxes shall be in accordance with<br />

the Massachusetts Electric Code.When an existing terminal<br />

box is to be replaced by the customer, NSTAR will, at<br />

customer request, de-energize the service at no cost. Upon<br />

completion of this replacement, and when approval has been<br />

received by the authority having jurisdiction, NSTAR will reenergize<br />

the service.<br />

Special Facilities:<br />

On installations requiring more than two service cables per<br />

phase, a special terminal facility may be required, especially in<br />

the Downtown Boston Network District of Boston.These<br />

installations, generally 800 amps and above, require the use of<br />

limiters as protective devices.The terminal facility is to be<br />

furnished, installed, owned and maintained by the customer<br />

under all circumstances. All special terminal facilities will be<br />

provided with a means for padlocking by NSTAR. Line-side<br />

connections will be made by NSTAR. All installations of this<br />

type will be coordinated through the NSTAR New Customer<br />

Connect Tech Center. See Sketch 9 for details. Installations<br />

greater than 1000 amps will require a limiter frame cabinet per<br />

ARTICLE 429-431<br />

NSTAR standards and must be coordinated through the<br />

NSTAR New Customer Connect Tech Center to arrange a site<br />

meeting with NSTAR Meter Operations. In addition, the<br />

customer must core drill or sleeve thru the foundation wall to<br />

connect 1-4 inch pvc per 400 amp of switch size (for example,<br />

an 800 amp switch requires 2-4 inch sleeves thru the<br />

foundation wall).<br />

429. Grounding and Bonding<br />

All secondary alternating current services having a grounded<br />

neutral shall have that neutral grounded on the customer’s<br />

premises at the service equipment as required by the<br />

Massachusetts Electrical Code.<br />

CUSTOMER <strong>REQUIREMENTS</strong> FOR PRIVATE<br />

PROPERTY INSTALLATIONS:<br />

430. Pole-Mounted Transformers<br />

Overhead services from a pole-mounted transformer on<br />

private property are restricted to installations where the<br />

required transformer capacity is 75 kVa or less for single<br />

phase, or 150 kVa or less for three phase. For installations<br />

exceeding the above values, a padmounted transformer is<br />

required.<br />

431. Mat and Fence Substation<br />

This type of private property installation is no longer available<br />

for new customers. It will be the responsibility of the existing<br />

customer to maintain the concrete transformer mat, liquid<br />

retaining curb where required by the authorities having<br />

jurisdiction, buried ground grid, stone fill, fence, and cable<br />

structure(s). Each of these items must meet NSTAR standards,<br />

which are available from the NSTAR New Customer Connect<br />

Tech Center.<br />