SKETCH 23<br />

Typical Meter Installation Involving Current Transformers One or<br />

More Cable Per Phase Each Cable No Larger Than 500 KCMIL<br />

SKETCH 24<br />

Transformer Rated Meter Installations With Meter Cabinet Located Outdoors<br />

METER SOCKET<br />

LOCATED OUTSIDE<br />

METER<br />

METER<br />

NOTE 2<br />

1 1/2" CONDUIT<br />

METER<br />

SOCKET<br />

<strong>SERVICE</strong><br />

SWITCH<br />

OR<br />

BREAKER<br />

LINE<br />

NEUTRAL BAR<br />

A<br />

D<br />

B<br />

CABLE<br />

CONNECTORS<br />

LOAD<br />

C - DEPTH<br />

SLIP METER RISER<br />

FOR PVC APPLICATION<br />

NOTE 3<br />

FINISHED GRADE<br />

6' - 0"<br />

5' - 4"<br />

NOTE 4<br />

1. See article 720 for more specific details on the requirements of the<br />

meter cabinet and associated equipment.<br />

TO NSTAR PADMOUNT XFMR<br />

SECONDARY SIDE<br />

2 FOOT IN CONCRETE<br />

1. All locations and installations are subject to NSTAR approval.<br />

2. Customer to supply and install NSTAR approved transformer rated<br />

meter socket. See article 720 for more specific details on the<br />

requirements of the meter cabinet and associated equipment.<br />

3. 4 foot channel iron 3/8 inch, painted.<br />

4. 1 1/2 inch EMT or PVC conduit with pull string.<br />

5.The location of the meter cabinet shall be a minimum of 3 feet but not<br />

to exceed 75 feet from the padmounted transformer or switchgear.<br />

6. A clear area of 3 feet is required in front of meter socket.<br />