Technical Information<br />

Motion detecto<strong>rs</strong><br />

© Siemens AG <strong>2011</strong><br />

Motion detector triac inserts (5TC1 501)<br />

■ Design<br />

I2_08812<br />

1<br />

2<br />

3<br />

4<br />

Motion detector<br />

Triac insert<br />

Frame<br />

Motion detector top<br />

Plug<br />

The motion detector triac insert $ is mounted in a DIN 49073-<br />

compliant device box.<br />

The terminals of the motion detector triac insert must be directed<br />

downwards (for wall mounting).<br />

Only use the motion detector triac insert in combination with a<br />

motion detector top &. Together with the frame %, the top is<br />

4<br />

3<br />

1<br />

2<br />

plugged onto the insert $. The electrical contacting is achieved<br />

over the plug (.<br />

Load conventional transforme<strong>rs</strong> with at least 85 % of the rated<br />

load with lamps.<br />

The total load including the transformer power loss must not exceed<br />

400 W/VA.<br />

Depending on the mounting type, the max. connected load must<br />

be reduced by:<br />

• –10 % each time the ambient temperature of 25 °C is<br />

exceeded by 5 °C,<br />

• –15 % for mounting on wood, Rigips or cavity walls,<br />

• –20 % for mounting in multiple combinations.<br />

Use of extension units<br />

The sensing field of the center unit can be extended by means<br />

of the motion detector extension unit insert.<br />

If mechanical pushbuttons are used (NO contacts), the lighting<br />

can be switched on from several sides irrespective of the current<br />

brightness level.<br />

Note: A motion detector top must be mounted on the center unit<br />

- otherwise, there will be no function.<br />

A mechanical pushbutton insert without a glow lamp <strong>and</strong> a motion<br />

detector extension unit insert may also be combined.<br />

■ Schematics<br />

5<br />

1 L<br />

1<br />

5TC1 501<br />

L<br />

N<br />

230 V AC 50/60 Hz<br />

5TC1 501<br />

1<br />

2<br />

N1 L<br />

5TC1 502<br />

2<br />

1 L<br />

3<br />

I2_08782a<br />

5TD2 120<br />

1<br />

Motion detector<br />

Triac insert<br />

I2_08783a<br />

2<br />

Load<br />

L N 4<br />

1<br />

2<br />

3<br />

4<br />

5<br />

Motion detector<br />

Triac insert<br />

Motion detector<br />

extension unit insert<br />

Mechanical pushbutton<br />

without a glow lamp<br />

Connection of further<br />

extension units<br />

Load<br />

19<br />

Connection of the motion detector triac insert<br />

Connection of all possible inserts<br />

19/44 Siemens <strong>ET</strong> <strong>D1</strong> · 10/2010