Process monitoring with analogue and relay outputs and display<br />

Micromann AR-SERIES<br />

Universal, galvanically-isolated signal converters<br />

with alarm function<br />

• External power supply<br />

• Pluggable connection terminals<br />

• Compact enclosure<br />

UHZAR<br />

Frequency input<br />

Process monitoring<br />

• Wide-range input<br />

• Supply of active input devices<br />

0 V +24 V<br />

9 10<br />

L<br />

H<br />

+12 V<br />

1<br />

Pull Up/Down<br />

2<br />

0 V<br />

3<br />

Input<br />

4<br />

+ Input<br />

5<br />

– Vin (High)<br />

6<br />

+<br />

PS<br />

V/I<br />

ch 1<br />

ch 2<br />

Common<br />

Iout / Vout<br />

+ Iout<br />

– Vout<br />

–<br />

11<br />

12<br />

13<br />

14<br />

15<br />

16<br />

Technical data<br />

Connections<br />

Input<br />

Input signal<br />

Input voltage<br />

Output analogue<br />

Type (analogue output)<br />

Load impedance, voltage/current<br />

Output current<br />

Output voltage<br />

Transmit function<br />

Alarm output<br />

Type<br />

Switching current<br />

Switching thresholds<br />

Display<br />

Type<br />

Display range<br />

Display value<br />

Resolution (display)<br />

General data<br />

Supply voltage<br />

Accuracy<br />

Linearity<br />

Temperature coefficient<br />

Long-term drift<br />

Step response time<br />

0...10 kHz<br />

50 mV...250 V AC/DC<br />

Voltage and current output (configurable)<br />

≥ 1 kΩ / ≤ 900 Ω<br />

0...22 mA<br />

0...11 V<br />

direct or inverted<br />

Alarm output with 2 NO contacts and suppressor circuit<br />

1 A @ 240 V AC / 30 V DC<br />

25 % of display range<br />

4-character display<br />

-999...9999<br />

Percentage or real value display<br />

0.001 of displayed value<br />

12...50 V DC<br />

< 0.5 % of measuring range<br />

< 0.05 % of signal range<br />

≤ 0.02 % / °C<br />

0.1 % / 10.000 h<br />

320 ms (10...90 %),<br />

Terminal <strong>Signal</strong><br />

1 12 V DC<br />

2 Pull Up / Down<br />

3 0 V<br />

4 <strong>Signal</strong> +<br />

5 <strong>Signal</strong> –<br />

6 High <strong>Signal</strong><br />

F<br />

Ambient temperature / Storage temperature<br />

Approvals<br />

Insulation coordination<br />

Insulation voltage<br />

Impulse withstand voltage<br />

Rated voltage<br />

EMC standards<br />

adjustable (250 ms...32 s)<br />

0 °C...+60 °C / -25 °C...+70 °C<br />

cULus; CE<br />

2 kV input / output / power supply<br />

4 kV (1.2/50 µs)<br />

300 V eff<br />

DIN EN 61326<br />

Dimensions<br />

Clamping range (nominal / min. / max.)<br />

Length x width x height<br />

Note<br />

mm²<br />

mm<br />

Screw connection<br />

1.5 / 0.5 / 2.5<br />

120 / 46 / 97<br />

PE connection direct on enclosure<br />

Ordering data<br />

Frequency converter<br />

Type Qty. Order No.<br />

UHZAR 1 7940010184<br />

Note<br />

Accessories<br />

F.11