19.01.2015 Views

Каталог Weidmuller: Electronics - Analogue Signal Conditioning

Каталог Weidmuller: Electronics - Analogue Signal Conditioning

Каталог Weidmuller: Electronics - Analogue Signal Conditioning

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

PROFIBUS-PA<br />

Fieldbus distributor<br />

The PROFIBUS-PA<br />

is an open fieldbus standard (EN 50170, IEC 1158-2,<br />

DIN 19245). It was specifically designed for the requirements<br />

of process engineering, such as remote powering and intrinsic<br />

safety. The PROFIBUS-PA enables operation of several PA<br />

sensors and actuators on one bus line.<br />

The devices are powered using twin cable technology, and the<br />

transmission of process data is digital.<br />

Technical data for PROFIBUS-PA standard distributors<br />

Temperature range<br />

Operating temperature from –40 °C to 85 °C<br />

Ingress protection class IP 66<br />

Housing material High-quality aluminium alloy (AL-Si 12)<br />

Surface Stove-enamelled RAL 7001<br />

PROFIBUS-PA connection Tension clamp connection 0.5 - 1.5 mm 2<br />

Cable entry<br />

Clamping range<br />

Measuring device connector M12 x 14-pin<br />

Information<br />

Cable gland M16<br />

5.5 - 9.5 mm<br />

Contacts MS, surface CUZnAu<br />

Integration in the PROFIBUS-DP network is done by means of<br />

a segment coupler.<br />

Specific advantages of PROFIBUS-PA:<br />

• Low wiring costs<br />

• Minimal planning costs for the process control system<br />

• Remote interrogation or programming of the field device<br />

• Further development and support by the PROFIBUS User<br />

Organisation<br />

Handling information<br />

Torques<br />

M16 gland to housing<br />

M16 union nut on cable gland<br />

Housing cover<br />

External earth stud<br />

6.25 Nm<br />

4.5 Nm<br />

1.8 - 2.0 Nm<br />

1.8 - 2.0 Nm<br />

Whether for servicing or system modification, the PROFIBUS-PA<br />

FB connectors from Weidmüller enable connection or replacement<br />

of field devices without interrupting the bus system.<br />

An extensive range of accessories such as pre-assembled<br />

cables and plug connectors rounds off the programme.<br />

J<br />

Shield is connected to the enclosure via the EMC cable glands.<br />

Thread the cable gland onto the seal, on the unprepared<br />

fieldbus cable<br />

Strip fieldbus cable here<br />

Fieldbus cable<br />

Shielding<br />

Draw back the shielding braid 8 50 … 70<br />

over the sheath of the fieldbus cable.<br />

Be sure to use wire-end ferrules!<br />

6<br />

J.11