ÐаÑалог Weidmuller: Electronics - Analogue Signal Conditioning
ÐаÑалог Weidmuller: Electronics - Analogue Signal Conditioning
ÐаÑалог Weidmuller: Electronics - Analogue Signal Conditioning
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
AMS400A<br />
Universal auto-manual stations<br />
• Display instrument for control panel installation<br />
• 1/8 DIN standard front<br />
• IP65 fully insulated<br />
• Pluggable connection terminals<br />
AMS400A<br />
Universal auto-manual stations<br />
Universal auto-manual stations<br />
Indicators and configurable<br />
displays<br />
H<br />
L<br />
W<br />
11<br />
12<br />
8<br />
9<br />
10<br />
Vin/Iin<br />
0 V<br />
Common<br />
<strong>Signal</strong> amplifier<br />
<strong>Signal</strong> reduction<br />
0 V<br />
1 2<br />
PS<br />
V/I<br />
+24 V<br />
Vout/Iout 3<br />
0 V<br />
4<br />
0 V<br />
5<br />
Automatic / manual 6<br />
Change operating mode 7<br />
NC<br />
13<br />
Common<br />
14<br />
NO 15<br />
NC 16<br />
Common<br />
17<br />
NO 18<br />
Technical data<br />
Display<br />
Type<br />
Display value<br />
Display range<br />
Input<br />
Type<br />
Input signal<br />
Input resistance<br />
Sampling rate<br />
Pulse width, min.<br />
Output<br />
Type<br />
Output analogue<br />
Output digital<br />
Output current<br />
Output voltage<br />
Last resistor, max.<br />
Alarm (RO version only)<br />
Type<br />
Number of channels<br />
Type of contact<br />
Ratings<br />
General data<br />
Supply voltage<br />
Power consumption<br />
Accuracy<br />
Repeat accuracy<br />
Temperature coefficient<br />
Cut-off frequency (-3 dB)<br />
Step response time<br />
Impulse withstand voltage<br />
Insulation voltage<br />
Ambient temperature / Storage temperature<br />
EMC standards<br />
Approvals<br />
Dimensions<br />
Clamping range (nominal / min. / max.)<br />
Length x width x height<br />
Note<br />
mm²<br />
mm<br />
4-digit, red LED, 14.2 mm<br />
Percentage or real value display<br />
-9999...9999<br />
Current input or digital input (pulse-controlled or no-voltage<br />
contact)<br />
0...24 mA / 0...12 V DC<br />
50 Ω (mA) / 10 MΩ (V)<br />
5x per sec. (current input)<br />
64 ms (digital input)<br />
<strong>Analogue</strong> and digital output<br />
Current or voltage, configured with jumper<br />
2 optocouplers, 50 V DC / 200 mA<br />
0...24 mA<br />
0...18 V<br />
900 Ω @ 20 mA<br />
Status relay<br />
2<br />
CO contact<br />
3 A @ 240 V AC or 5 A @ 24 V DC<br />
24 V DC ± 10 %, other voltages on request<br />
6 W @ 24 V DC<br />
Typically ± 0.1 % of signal range<br />
± 0.02 % of signal range<br />
< 0.02 % / °C<br />
5 Hz<br />
300 ms (10...90 %)<br />
4 kV (1.2/50 µs)<br />
1 kV input / output / power supply<br />
0 °C...+60 °C / -25 °C...+70 °C<br />
DIN EN 61326<br />
cULus; CE<br />
Screw connection<br />
1.5 / 0.5 / 2.5<br />
137 / 96.6 / 48.8<br />
Connections<br />
Terminal <strong>Signal</strong><br />
1 –<br />
Supply voltage<br />
2 +<br />
3 <strong>Signal</strong> +<br />
<strong>Analogue</strong> Output<br />
4 <strong>Signal</strong> –<br />
5 <strong>Signal</strong> – 0 V<br />
6 Automatic / manual Status outputs<br />
7 Change operating mode<br />
8 Common<br />
9 <strong>Signal</strong> amplifier Digital inputs<br />
10 <strong>Signal</strong> reduction<br />
<strong>Analogue</strong> inputs<br />
13 NC contact<br />
Relay output,<br />
14 Common<br />
signal amplifier<br />
15 NO contacts<br />
16 NC contact<br />
Relay output,<br />
17 Common<br />
signal reduction<br />
18 NO contacts<br />
11 <strong>Signal</strong> +<br />
12 <strong>Signal</strong> –<br />
G<br />
Ordering data<br />
Connection system<br />
<strong>Analogue</strong> output<br />
<strong>Analogue</strong> and relay output<br />
Type Qty. Order No.<br />
AMS400A 4-20mA/AO 1 7940011895<br />
AMS400A 4-20mA/AO/RO 1 7940015937<br />
Note<br />
Accessories<br />
G.17