Labelling for ATEX approval of a signal converter<br />

ATEX<br />

Technical appendix/Glossary<br />

II 3 G Ex nAnCnL IIC T4<br />

II (1) D [Ex iaD]<br />

II = Device group 2: devices for use in hazardous areas<br />

(except for mines and above-ground mining facilities<br />

that are exposed to flammable dusts or methane)<br />

3 = Device category 3: the danger occurs rarely or only<br />

for short periods. The requirement is for normal<br />

security, suitable for use in zone 2.<br />

G = Intended for the gas zone<br />

Ex = Explosion protection<br />

nA = Non-sparking equipment<br />

nC = Enclosed facility (suitable protection)<br />

nL = Equipment with limited power<br />

IIC = Explosion groups: typical gas for C is hydrogen<br />

T4 = Temperature class The max. permitted surface<br />

temperature for T4 is 135 °C<br />

II = Device group 2: devices for use in hazardous areas<br />

(except for mines and above-ground mining facilities<br />

that are exposed to flammable dusts or methane)<br />

(1) = Device category (1): Equipment from category 1 can<br />

be connected to this signal converter. The signal<br />

converter must be operated in the safe zone or in<br />

zone 2 (II 3 G …).<br />

D = Designed for the dust zone.<br />

[Ex iaD] = Explosion protection type: protected with intrinsic<br />

safety. This signal converter, as accompanying<br />

equipment, in intended to be used for the connection<br />

of intrinsically safe circuits.<br />

Zone 2 a zone for which during normal operations there is<br />

at most only a short-term occurrence of dangerous<br />

hazardous atmospheres (mixtures of air and flammables<br />

gases, vapours or mists).<br />

II (1) G [Ex ia] IIC/IIB/IIA<br />

II = Device group 2: devices for use in hazardous areas<br />

(except for mines and above-ground mining facilities<br />

that are exposed to flammable dusts or methane)<br />

(1) = Device category (1): Equipment from category 1 can<br />

be connected to this signal converter. The signal<br />

converter must be operated in the safe zone or in<br />

zone 2 (II 3 G …).<br />

G = Intended for the gas zone.<br />

[Ex ia] = Explosion protection type: protected with intrinsic<br />

safety. This signal converter, as accompanying<br />

equipment, in intended to be used for the connection<br />

of intrinsically safe circuits.<br />

IIC/ = Explosion groups – typical gases: propane for A,<br />

IIB/IIA Ethylene for B, and hydrogen for C.<br />