Modules<br />

Voltage supply<br />

PSSu E F BSW(-T)<br />

Switching an earthed actuator<br />

[ . . . ]<br />

PSSu E F BSW(-T)<br />

Output module (ST)<br />

Output module (ST)<br />

Output module (ST)<br />

Output module (ST)<br />

Module Supply<br />

[ . . . ]<br />

3.3<br />

[ . . . ]<br />

+24 V DC<br />

0 V DC<br />

L1<br />

N<br />

~<br />

=<br />

Fuse<br />

+24 V DC<br />

0 V<br />

Actuator<br />

Periphery Supply<br />

On earthed actuators, the actuator's<br />

0 V connection must be connected to<br />

0 V of the periphery supply (external<br />

supply voltage).<br />

Reason: The switch (0 V periphery<br />

supply) in the PSSu E F BSW module<br />

is bridged when the actuator's earthed<br />

0 V connection is connected to 0 V on<br />

the connected periphery supply. In<br />

this case, the PSSu E F BSW registers<br />

a short circuit between 0 V of the external<br />

supply voltage and 0 V of the<br />

connected periphery supply.<br />

Error reaction: The PSSu will not start<br />

and all affected I/O-Groups (Safety-<br />

BUS p) remain in a STOP condition.<br />

3.3-32<br />

<strong>Pilz</strong> <strong>GmbH</strong> & <strong>Co</strong>. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany<br />