Modules<br />

Voltage supply<br />

PSSu E F BSW(-T)<br />

<strong>Co</strong>nnection<br />

][Anschlus BSW<br />

11<br />

21<br />

Periphery Supply<br />

12<br />

22<br />

13<br />

23<br />

14<br />

24<br />

3.3<br />

0 V DC<br />

+24 V DC<br />

=<br />

~<br />

Fuse<br />

PSSu E F BSW/<br />

PSSu E F BSW-T with<br />

- PSSu BS 2/8S(-T)<br />

- PSSu BS 2/8C(-T)<br />

C-rail supply<br />

L1<br />

N<br />

<strong>Co</strong>nnect to the 0 V supply and<br />

earth at a single point<br />

If you are using actuators for safety-related<br />

functions, it is essential that you<br />

note the following:<br />

A safety assessment must be made<br />

for each individual application.<br />

Input modules may not be used<br />

within an output block. If an error<br />

occurs, input modules could supply<br />

an external voltage which cannot<br />

be switched off.<br />

The position of each single actuator<br />

must be monitored, e.g. via an FS<br />

feedback loop with test pulses.<br />

To prevent contact welding, a fuse<br />

should be connected before the periphery<br />

supply infeed (see Technical<br />

details).<br />

The following applies for floating<br />

actuators:<br />

All actuator masses must be fed<br />

back to the output modules.<br />

The following applies for earthed<br />

actuators:<br />

The possibility of a short circuit to +<br />

24 V of the external supply voltage<br />

must be excluded.<br />

When using modules of type<br />

PSSu E PD in an output block, please<br />

note the following:<br />

Do not connect capacitive loads.<br />

During the power-up test, the relay<br />

contacts are tested with pulses of<br />

up to 60 ms.<br />

<strong>Co</strong>nnection example<br />

Block switching with dual-channel<br />

operation and redundant actuator.<br />

The ST output module PSSu E S<br />

4DO 0.5 belongs to the output<br />

block of the PSSu E F BSW module.<br />

The FS input module for forming the<br />

feedback loop (PSSu E F 4DI with<br />

test pulses) belongs to another supply<br />

group, which is not shut down.<br />

A maximum of Cat. 3 in accordance<br />

with EN 954-1 and SIL2 in accordance<br />

with EN IEC 61508 can be<br />

achieved.<br />

3.3-34<br />

<strong>Pilz</strong> <strong>GmbH</strong> & <strong>Co</strong>. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany<br />

Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: pilz.gmbh@pilz.de<br />

PSSu-2011-01