<strong>System</strong> environment B basics<br />

<strong>System</strong> <strong>description</strong><br />

Maximum system expansion<br />

Maximum current load capacity on the supply voltage modules<br />

][Max. Ausbau Strom Versorgungsmodule Sys A + B<br />

2.1<br />

<strong>System</strong> supply<br />

Module supply when supplied via<br />

- PSSu E F PS(-T)<br />

Module supply when supplied via<br />

- PSSu E F PS1(-T)<br />

Periphery supply<br />

C-rail<br />

Max. current load<br />

1.5 A<br />

2 A<br />

10 A<br />

10 A<br />

][Max. Ausbau Strom Belastung Sys A + B<br />

Module supply<br />

The module supply's current load is<br />

the total current consumption resulting<br />

from the electronic modules<br />

and compact modules. If the total<br />

current consumption is higher than<br />

the supply module's current load<br />

capacity, the module supply must<br />

be refreshed with an additional supply<br />

module (see modules' technical<br />

details). The system software takes<br />

this into account.<br />

Periphery supply<br />

Maximum current load: 10 A<br />

The current load of the periphery<br />

supply is the sum of the current<br />

consumption of the sensors and<br />

actuators supplied via the input/<br />

output modules. If the current load<br />

is higher, the periphery supply must<br />

be refreshed with an additional supply<br />

module to prevent overload.<br />

Please refer to the derating diagram.<br />

C-rail<br />

Maximum current load: 10 A<br />

If the current load is higher, the<br />

C-rail must use a different supply to<br />

prevent overload. Please refer to<br />

the derating diagram.<br />

Maximum current load capacity<br />

based on temperature<br />

Formatierung_Fliess_ueber_alle_Spalten<br />

][Max. Strombelastbarkeit Derating Sys A + B<br />

The maximum current load capacity of<br />

the module bus with regard to the periphery<br />

supply and C-rail can only be<br />

achieved if the max. permitted ambient<br />

temperature is adhered to.<br />

Derating diagram for periphery supply and C-rail: Temperature T dependent on load current I<br />

T [°C]<br />

100<br />

80<br />

60<br />

40<br />

20<br />

0<br />

1 2 3 4 5 6 7 8 9 10<br />

I [A]<br />

2.1-12<br />